K-23
E6581531
11
[24] Meter output
Sensorless vector/vector with sensor (
●
:Effective, -:Ineffective)
Default setting
Title
Communication
No.
Function Adjustment
range
Minimum
setting unit
(Panel/Communi
cation)
V[R
=
500V
-50Hz
V[R
=
575V
-60Hz
V[R
=
690V
-50Hz
Write
during
running
Vector
control
V/f
Constant
Reference
CO
0671
AM terminal meter adjustment
-
1/1
-
-
-
Enabled
●
/
●
●
5. 16
H
0672
MON1 terminal meter selection
0~76 *1
1/1
4 4 4
Enabled
●
/
●
●
*2
H
0673
MON1 terminal meter adjustment
-
1/1
- - -
Enabled
●
/
●
●
*2
H
0674
MON2 terminal meter selection
0~76 *1
1/1
5 5 5
Enabled
●
/
●
●
*2
H
0675
MON2 terminal meter adjustment
-
1/1
- - -
Enabled
●
/
●
●
*2
H
0676
Pulse output function selection
0~49 *1
1/1
0 0 0
Enabled
●
/
●
●
6. 30. 1
H
0677
Selection of number of pulses
1.00~43.20kHz
0.01/0.01
3.84
3.84
3.84
Enabled
●
/
●
●
6. 30. 1
H
0678
Constant at the time of filtering
4msec, 8msec~100msec
1/1
64 64 64
Enabled
●
/
●
●
5.
16
H
0681
FM voltage/current output switching
0:Voltage 0~10V output
1:Current 0~20mA output
1/1
0 0 0
Disabled
●
/
●
●
6. 30. 3
H
0682
FM output gradient characteristic
0:Negative gradient (descending)
1:Positive gradient (ascending)
1/1 1 1 1
Enabled
●
/
●
●
6. 30. 3
H
0683 FM
bias
adjustment
-10.0~100.0%
0.1/0.1 0.0 0.0 0.0
Enabled
●
/
●
●
6. 30. 3
H
0684
FM output filter
0:No filter
1:Filter approx. 10ms
2:Filter approx. 15ms
3:Filter approx. 30ms
4:Filter approx. 60ms
5:Filter approx. 120ms
6:Filter approx. 250ms
7:Filter approx. 500ms
8:Filter approx. 1s
1/1
0 0 0
Enabled
●
/
●
●
5.
16
H
0685
AM output gradient characteristic
0:Negative inclination (downward slope)
1:Positive inclination (upward slope)
1/1 1 1 1
Enabled
●
/
●
●
6. 30. 3
H
0686
AM bias adjustment
-10.0~100.0%
0.1/0.1
0.0 0.0 0.0
Enabled
●
/
●
●
6. 30. 3
H
0688
MON1 voltage/current output switching
0:Voltage -10~10V output
1:Voltage 0~10V output
2:Current 0~20mA output
1/1
1 1 1
Disabled
●
/
●
●
*2
H
0689
MON1 output gradient characteristic
0:Negative inclination (downward slope)
1:Positive inclination (upward slope)
1/1 1 1 1
Enabled
●
/
●
●
*2
H
0690
MON1 bias adjustment
-10.0~100.0%
0.1/0.1
0.0 0.0 0.0
Enabled
●
/
●
●
*2
H
0691
MON2 voltage/current output switching
0:Voltage -10~10V output
1:Voltage 0~10V output
2:Current 0~20mA output
1/1
1 1 1
Disabled
●
/
●
●
*2
H
0692
MON2 output gradient characteristic
0:Negative inclination (downward slope)
1:Positive inclination (upward slope)
1/1 1 1 1
Enabled
●
/
●
●
*2
H
0693
MON2 bias adjustment
-10.0~100.0%
0.1/0.1
0.0 0.0 0.0
Enabled
●
/
●
●
*2
This parameter moves to a fundamental parameter.
*1:
⇒
For the adjustment range, see the table on page K-39.
*2:
⇒
For details, refer to Instruction Manual (E6581341) specified in Section 6.36.