10
Power supply voltage 600V
Wire size (For UL508C)
Main circuit
Input terminal
(R/L1, S/L2, T/L3)
Output terminal
(U/T1, V/T2, W/T2)
DC terminal
Earth cable
Inverter model
Applicable
motor
(HP)
AWG AWG AWG AWG
VFPS1-5022PM 3HP
14
14
14
14
VFPS1-5040PM 5HP
14
14
10
14
VFPS1-5055PM 7.5HP
12
14
10
14
VFPS1-5075PM 10HP
10
14
8
12
VFPS1-6150PL 15HP
8
8
8
10
VFPS1-6185PL 20HP
8
8
8
10
VFPS1-6220PL 25HP
6
6
6
10
VFPS1-6300PL 30HP
4
4
4
10
VFPS1-6370PL 40HP
3
3
3
8
VFPS1-6450PL 50HP
2
2
2
8
VFPS1-6550PL 60HP
2
2
2
8
VFPS1-6750PL 75HP
1/0
1/0
1/0
6
VFPS1-6900PL 100HP
2/0
2/0
2/0
6
VFPS1-6110KPC
125HP 2/0
2/0
2/0
6
VFPS1-6132KPC
150HP 250MCM 250MCM 250MCM
2
VFPS1-6200KPC
200HP 300MCM 300MCM 300MCM
2
VFPS1-6250KPC
250HP 250MCMx2
250MCMx2
250MCMx2
1
VFPS1-6315KPC
350HP 350MCMx2
350MCMx2
350MCMx2
2/0
VFPS1-6400KPC
450HP 350MCMx3
350MCMx3
350MCMx3
3/0
VFPS1-6500KPC
550HP 300MCMx2x2(*4)
300MCMx4
300MCMx4
4/0
VFPS1-6630KPC
700HP 400MCMx2x2(*4)
400MCMx4
400MCMx4
4/0
Power supply voltage 690V
Wire size (For IEC60364-5-52)
Main circuit
Input terminal
(R/L1, S/L2, T/L3)
Output terminal
(U/T1, V/T2, W/T2)
DC terminal
Earth cable
Inverter model
Applicable
motor
(kW)
mm
2
mm
2
mm
2
mm
2
VFPS1-6030PL 3
1.5
1.5
2.5
2.5
VFPS1-6055PL 5.5
2.5
1.5
2.5
2.5
VFPS1-6075PL 7.5
2.5
1.5
4
2.5
VFPS1-6110PL 11
4
2.5
4
4
VFPS1-6150PL 15
6
2.5
6
6
VFPS1-6185PL 18.5
10
4
10
10
VFPS1-6220PL 22
10
4
10
10
VFPS1-6300PL 30
10
6
10
10
VFPS1-6370PL 37
16
10
16
16
VFPS1-6450PL 45
25
16
25
16
VFPS1-6550PL 55
35
16
35
16
VFPS1-6750PL 75
50
25
50
25
VFPS1-6900PL 90
70
35
70
35
VFPS1-6110KPC
110 70 70 70 35
VFPS1-6132KPC
132 95 70 95 50
VFPS1-6160KPC
160 120
95
120
70
VFPS1-6200KPC
185 185
120
185
95
VFPS1-6250KPC
250 120x2
185
120x2
150
VFPS1-6315KPC
315 150x2
120x2
150x2
150
VFPS1-6400KPC
400 185x2 150x2 150x3 185
VFPS1-6500KPC
500 185x3 150x3 185x3 150x2
VFPS1-6630KPC
630 185x4 185x3 185x4 185x2
(*1): The recommended cable size is that of the cable (e.g. 1500V class, cupper cable) with continuous maximum permissible temperature of 75°C.
Ambient temperature is 40°C or less and the wiring distance is 30m or less.
(*2): For the control circuit, use shielded wires whose size (cross-section) is 0.75 mm
2
or more.
(*3): For the earth cable, use wires larger than the specified ones in size (cross-section).
(*4): The number refers to a cable composition. For example, in the case of “120×2×2”: 120×2×2
Содержание TOSVERT VF-PS1
Страница 1: ......
Страница 19: ...E6581531 A 7 1 VFPS1 6370PL 6900PL VFPS1 6110KPC 6200KPC ...
Страница 20: ...E6581531 A 8 1 VFPS1 6250KPC 6400KPC VFPS1 6500KPC 6630KPC ...
Страница 30: ...E6581531 A 18 1 VFPS1 6250KPC 6315KPC 6400KPC VFPS1 6500KPC 6630KPC ...
Страница 317: ......