![Toshiba TOSVERT VF-PS1 Скачать руководство пользователя страница 204](http://html.mh-extra.com/html/toshiba/tosvert-vf-ps1/tosvert-vf-ps1_instruction-manual_424777204.webp)
E6581531
G-9
7
Sink logic/source logic
Sink logic and source logic (logic of input/output terminal) can be switched to each other.
⇒
For details, refer to Section 2.3.2.
7.2.3 Analog input filter
Response time setting
Title
Function
Adjustment range
Default setting
H
Analog input filter
:No filter
:Filter approx. 10ms
:Filter approx. 15ms
:Filter approx. 30ms
:Filter approx. 60ms
•Function
This function is effective to remove noise from the frequency setting circuit. If operation is unstable because of
noise, increase the time constant of the analog input filter.