E6581531
F-6
6
6.3 Terminal
function
selection
6.3.1 Keeping an input terminal function always active (ON)
H
,
H
,
H
: Always ON function selection 1~3
• Function
This parameter specifies an input terminal function that is always kept active (ON). (Only one function
selectable)
[Parameter setting]
Title
Function
Adjustment range
Default setting
H
Always ON function selection 1
~
H
Always ON function selection 2
~
H
Always ON function selection 3
~
* The selected function is always kept active regardless of the type of logic (positive or negative) in the table of
function settings in 7.2.1.
6.3.2 Modifying input terminal functions
H
: Input terminal function selection 1 (F)
H
: Input terminal function selection 2 (R)
H
: Input terminal function selection 4 (RES)
H
: Input terminal function selection 5 (S1)
H
: Input terminal function selection 6 (S2)
H
: Input terminal function selection 7 (S3)
H
: Input terminal function selection 8
(RR/S4)
H
~
H
:
Input terminal function selection 9~16
⇒
For details, refer to Section 7.2.1.
• Function
Use the above parameters to send signals from an external programmable controller to various control input
terminals to operate and/or set the inverter.
The desired contact input terminal functions can be selected from about 80 types (
-
). This gives system
design flexibility.
Using the SW3 switch, the function of the RR/S4 terminal can be selected between analog input and contact
input. By default, the RR/S4 terminal is set as an analog input terminal (voltage input terminal). To use it as a
contact input terminal, therefore, you need to turn the SW3 switch to the S4 position.
Setting of contact input terminal function
Terminal
symbol
Title Function
Adjustment
range
Default
setting
–
H
Always ON function selection 1
(ST)
–
H
,
H
Always ON function selection 2, 3
F
H
Input terminal function selection 1 (F)
(F)
R
H
Input terminal function selection 2 (R)
(R)
RES
H
Input terminal function selection 4 (RES)
(RES)
S1
H
Input terminal function selection 5 (S1)
(S1)
S2
H
Input terminal function selection 6 (S2)
(S2)
S3
H
Input terminal function selection 7 (S3)
~
(
⇒
Refer to
Section 11.)
(S3)
The terminal below is operative only when SW3 is in the S4 position.
–
–
RR/S4
H
Input terminal function selection 7 (S4)
~
[Note 2]
(S4)
Note 1: The function that has been selected using
H
,
H
and
H
(always ON function selection 1~3
parameter) are always activated.
Note 2: When using the RR/R4 terminal as a contact input terminal (sink logic), always turn the SW3 slide switch to
the S4 position.