K-10
E6581531
11
[9] Jogging operation
Sensorless vector/vector with sensor (
●
:Effective, -:Ineffective)
Default setting
Title
Communication
No.
Function Adjustment
range
Minimum
setting unit
(Panel/Communi
cation)
V[R
=
500V
-50Hz
V[R
=
575V
-60Hz
V[R
=
690V
-50Hz
Write
during
running
Vector
control
V/f
Reference
H
0260 Jog
run
frequency
H
~20.0Hz 0.1/0.01
5.0 5.0 5.0
Enabled
●
/
●
●
6.
10
H
0261
Jog run stop pattern
0:Deceleration stop
1:Coast stop
2:DC braking stop
1/1
0 0 0
Disabled
●
/
●
●
6.
10
H
0262
Operation panel jog run mode
0:Disabled
1:Operation panel jog run mode enabled
1/1
0 0 0
Enabled
●
/
●
●
6.
10
H
0264
Input from external contacts - UP
response time
0.0~10.0 sec.
0.1/0.1
0.1 0.1 0.1
Enabled
●
/
●
●
6.
11
H
0265
Input from external contacts - UP
frequency step
0.0~
HJ
Hz
0.1/0.01
0.1 0.1 0.1
Enabled
●
/
●
●
6.
11
H
0266
Input from external contacts - DOWN
response time
0.0~10.0 sec.
0.1/0.1
0.1 0.1 0.1
Enabled
●
/
●
●
6.
11
H
0267
Input from external contacts - DOWN
frequency step
0.0~
HJ
Hz
0.1/0.01
0.1 0.1 0.1
Enabled
●
/
●
●
6.
11
H
0268 Initial
UP/DOWN
frequency
NN
~
WN
Hz
0.1/0.01
0.0 0.0 0.0
Enabled
●
/
●
●
6.
11
H
0269
Initial up/down frequency rewriting
0:Not changed
1:Setting of
H
changed when power is
turned off
1/1
1 1 1
Enabled
●
/
●
●
6.
11
[10] Jump frequency
Sensorless vector/vector with sensor (
●
:Effective, -:Ineffective)
Default setting
Title
Communication
No.
Function Adjustment
range
Minimum
setting unit
(Panel/Communi
cation)
V[R
=
500V
-50Hz
V[R
=
575V
-60Hz
V[R
=
690V
-50Hz
Write
during
running
Vector
control
V/f Reference
H
0270
Jump frequency 1
0.0~
HJ
Hz
0.1/0.01
0.0
0.0
0.0
Enabled
●
/
●
●
6.
12
H
0271 Jumping
width
1
0.0~30.0Hz
0.1/0.01
0.0
0.0
0.0
Enabled
●
/
●
●
6.
12
H
0272
Jump frequency 2
0.0~
HJ
Hz
0.1/0.01
0.0
0.0
0.0
Enabled
●
/
●
●
6.
12
H
0273 Jumping
width
2
0.0~30.0Hz
0.1/0.01
0.0
0.0
0.0
Enabled
●
/
●
●
6.
12
H
0274
Jump frequency 3
0.0~
HJ
Hz
0.1/0.01
0.0
0.0
0.0
Enabled
●
/
●
●
6.
12
H
0275 Jumping
width
3
0.0~30.0Hz
0.1/0.01
0.0
0.0
0.0
Enabled
●
/
●
●
6.
12
[11] Preset speed operation frequency (8~15) [1/2]
Sensorless vector/vector with sensor (
●
:Effective, -:Ineffective)
Default setting
Title
Communication
No.
Function Adjustment
range
Minimum
setting unit
(Panel/Communi
cation)
V[R
=
500V
-50Hz
V[R
=
575V
-60Hz
V[R
=
690V
-50Hz
Write
during
running
Vector
control
V/f
Reference
H
0287
Preset speed operation frequency 8
NN
~
WN
Hz
0.1/0.01
0.0
0.0
0.0
Enabled
●
/
●
●
5. 12
H
0288
Preset speed operation frequency 9
NN
~
WN
Hz
0.1/0.01
0.0
0.0
0.0
Enabled
●
/
●
●
5. 12
H
0289
Preset speed operation frequency 10
NN
~
WN
Hz
0.1/0.01
0.0
0.0
0.0
Enabled
●
/
●
●
5. 12