E6581531
B-9
2
[Standard connection diagram - source logic]
The figure below shows an example of typical wiring in the main circuit VFPS1-6500KPC to 6630KPC inverter.
*1: AC reactor (PFL): Mandatory for VFPS1-6110KPC and above.
*2: Transformer for fan supply (TRS)
⇒
Refer to section 1.4.4.
*3:
⇒
Refer to Section 2.3.2 for switch functions.
*4: The functions assigned to terminals OUT1, VI/II and RR/S4 can be switched by changing parameter settings.
⇒
For details refer to Section 2.3.2.
*5: To supply control power from an external power supply for backing up the control power supplied from the inverter, an
optional control power backup device (CPS002Z) is required. In such a case, the backup device is used at the same time
with the internal power supply of the inverter.
To back up control power, set the parameter
H
(Control power supply backup option failure monitoring) properly.
⇒
For more information, refer to 6.33.24.
*6: For PWR connection conforming to safety standards, refer to Section 9.3.
*7: If you use a braking unit and external braking resister in combination.
*8: TRS(Transformer for fan power supply) can not be used this system for VFPS1-6110KPC and above.