E6581531
E-26
5
5.16
Meter setting and adjustment
HOUN
: FM terminal meter selection
HO
: FM terminal meter adjustment
H
: Constant at the time of filtering
H
: FM voltage/current output
switching
H
: Inclination characteristic of FM
output
H
: FM bias adjustment
H
: FM output filter
COUN
: AM terminal meter
selection
CO
: AM terminal meter
adjustment
H
: Inclination characteristic
of AM output
H
: AM bias adjustment
Note 1: The signal output from the FM and AM terminal is an analog voltage signal or an analog current signal.
(positive (+) side output. For signed data, an absolute value is output. To output data with positive and
negative sings, you need to use two extended terminal boards (optional).)
Note 2: To the FM terminal, connect either a full-scale 0~1mAdc ammeter or a full-scale 0~7.5Vdc (or 10Vdc)
voltmeter, if necessary. The FM terminal can also be used as a 0(4)~20mAdc output terminal.
To the AM terminal, connect either a full-scale 0~1mAdc ammeter or a full-scale 0~7.5Vdc (or 10Vdc)
voltmeter, if necessary.
Connect meters as shown below.
<Connection to terminal FM>
FM
CCA
VF-PS1
The reading of the frequency meter fluctuates during calibration.
Meter: Frequency meter
(default setting)
+
-
A frequency meter QS60T is optionally available.
Output modes of the FM terminal
0-10V
0-20mA
0-1mA
FM
When used with a 0~1mAdc ammeter
(Default setting)
SW2
When the optional frequency meter QS60T is
connected, this mode is selected.
0-10V
0-20mA
0-1mA
FM
When used with a DC0~10V voltmeter
SW2
H
=
0-10V
0-20mA
0-1mA
FM
When used with a 0(4)~20mAdc
SW2
H
=
<Connection to terminal AM >
AM
CCA
VF-PS1
The reading of the ammeter fluctuates during calibration.
Meter: Ammeter
(default setting)
+
-
It is recommendable to use an ammeter with a current rating 1.5 or more times as high as the output current
rating of the inverter.
• Function
Inverter’s operation data is sent to the FM terminal (AM terminal) as analog voltage signals or analog current
signals. To display inverter’s operation data, connect a meter to this terminal. The “FM terminal-connected meter
adjustment
HO
” (AM terminal-connected meter adjustment
CO
) parameter is used to calibrate the meter
.