E6581531
E-38
5
Minimum resistance of connectable braking resistors
The minimum allowable resistance values of the externally connectable braking resistors are listed in the table
below.
Do not connect braking resistors with smaller resultant resistance than the listed minimum allowable resistance
values.
(For 250kW or greater models, a dynamic braking resistor drive unit (optional separate unit) is needed.)
Inverter
Related output capacity
Inverter type
500V 600V
690V
Minimum
allowable
resistance
VFPS1-5022PM 2.2kW 3HP
25
Ω
VFPS1-5030PM 3.0kW
-
25
Ω
VFPS1-5040PM 4kW 5HP
25
Ω
VFPS1-5055PM 5.5kW 7.5HP
25
Ω
VFPS1-5075PM 7.5kW 10HP
25
Ω
VFPS1-6030PL 2.2kW 3HP
3kW
12
Ω
VFPS1-6055PL 4kW 5HP
5.5kW
12
Ω
VFPS1-6075PL 5.5kW 7.5HP
7.5kW
12
Ω
VFPS1-6110PL 7.5kW 10HP
11kW
12
Ω
VFPS1-6150PL 11kW 15HP
15kW
12
Ω
VFPS1-6185PL 15kW 20HP
18.5kW
12
Ω
VFPS1-6220PL 18.5kW 25HP
22kW
12
Ω
VFPS1-6300PL 22kW 30HP
30kW
12
Ω
VFPS1-6370PL 30kW 40HP
37kW
12
Ω
VFPS1-6450PL 37kW 50HP
45kW
8
Ω
VFPS1-6550PL 45kW 60HP
55kW
8
Ω
VFPS1-6750PL 55kW 75HP
75kW
5
Ω
VFPS1-6900PL 75kW
100HP
90kW
5
Ω
VFPS1-6110KPC 90kW 125HP
110kW
4
Ω
VFPS1-6132KPC 110kW 150HP
132kW
4
Ω
VFPS1-6160KPC 132kW
-
160kW
4
Ω
VFPS1-6200KPC 160kW 200HP
200kW
4
Ω
VFPS1-6250KPC 185kW 250HP
250kW
2
Ω
VFPS1-6315KPC 250kW 350HP
315kW
2
Ω
VFPS1-6400KPC 315kW 450HP
400kW
2
Ω
VFPS1-6500KPC 400kW 550HP
500kW
1
Ω
VFPS1-6630KPC 500kW 700HP
630kW
1
Ω
Note 1: PB7-6
: Braking unit (Connected to PA/+, PC/- terminal)
Combined braking resistor (Connected to PA/+, PB terminal of PB7-6
)
Содержание TOSVERT VF-PS1
Страница 1: ......
Страница 19: ...E6581531 A 7 1 VFPS1 6370PL 6900PL VFPS1 6110KPC 6200KPC ...
Страница 20: ...E6581531 A 8 1 VFPS1 6250KPC 6400KPC VFPS1 6500KPC 6630KPC ...
Страница 30: ...E6581531 A 18 1 VFPS1 6250KPC 6315KPC 6400KPC VFPS1 6500KPC 6630KPC ...
Страница 317: ......