6.26 Protection
functions
6.26.1 Setting of stall prevention level
H
: Stall prevention level
Warning
Prohibited
• Do not set the stall prevention level (
H
) extremely low.
If the stall prevention level parameter (
H
) is set at or below the no-load current of the motor, the stall
preventive function will be always active and increase the frequency when it judges that regenerative
braking is taking place.
Do not set the stall prevention level parameter (
H
) below 30% under normal use conditions.
• Function
This parameter reduces the output frequency by activating a current stall prevention function against a
current exceeding the
H
-specified level.
[Parameter setting]
Title
Function
Adjustment range
Default setting
H
Stall prevention level
~
%,
:Deactivated
[Display during the alarm
QE
]
During an
QE
alarm status, (that is, when there is a current flow in excess of the stall prevention level), the output
frequency changes. At the same time, to the left of this value, “
E
” is displayed flashing on and off.
Example of display
6.26.2 Stall prevention control switching
H
: Stall prevention control switching
• Function
The operation of the stall prevention control can be switched. Set
H
=
when the overvoltage trip
are displayed when acceleration and the deceleration are switched. This parameter is effective at only V/F
control mode(
RV
=
,
,
) .
[Parameter setting]
Title
Function
Adjustment range
Default setting
H
Stall prevention control switching
: Stall prevention control 1
: Stall prevention control 2
6.26.3 Inverter trip record retention
H
: Inverter trip record retention selection
• Function
If the inverter trips, this parameter will retain the corresponding trip information. Trip information that has
thus been stored into memory can be displayed, even after power has been reset.
[Parameter setting]
Title
Function
Adjustment range
Default setting
H
Inverter trip record retention selection
:Clear when power is turned off.
:Retain even after power is turned off.
Up to four sets of latest trip records displayed in status monitor mode can be stored into memory.