UPS for 480 Vac Grid, User Guide, doc. rel. 4.0
186
Register
Variable name
GET Values
Remarks
21
4x0021
Input Voltage Line 3
×10 Vac
Divide the value by 10 for real measurement:
2315/10=231.5 Vac
22
4x0022
Input Current Line 3
×10 A
Divide the value by 10 for real measurement:
21/10=2.1 A
24
4x0024
Output Source
0: Normal
1: On Battery
2: On Bypass
3: Reducing
4: Boosting
5: Other
6: None
Depends on the UPS topology
25
4x0025
Output Frequency
×10 Hz
Divide the value by 10 for real measurement:
502/10=50.2 Hz
26
4x0026
Output Number of Lines 1 to 3
Number of the UPS output phases
27
4x0027
Output Voltage Line 1
×10 Vac
Divide the value by 10 for real measurement:
2315/10=231.5 Vac
28
4x0028
Output Current Line 1
×10 A
Divide the value by 10 for real measurement:
21/10=2.1 A
30
4x0030
Output Load Line 1
%
Some units might show values over 100% in
case of overload
31
4x0031
Output Voltage Line 2
×10 Vac
Divide the value by 10 for real measurement:
2315/10=231.5 Vac
32
4x0032
Output Current Line 2
×10 A
Divide the value by 10 for real measurement:
21/10=2.1 A
34
4x0034
Output Load Line 2
%
Some units might show values over 100% in
case of overload
35
4x0035
Output Voltage Line 3
×10 Vac
Divide the value by 10 for real measurement:
2315/10=231.5 Vac
36
4x0036
Output Current Line 3
×10 A
Divide the value by 10 for real measurement:
21/10=2.1 A
38
4x0038
Output Load Line 3
%
Some units might show values over 100% in
case of overload
39
4x0039
Bypass Frequency
×10 Hz
Divide the value by 10 for real measurement:
502/10=50.2 Hz
40
4x0040
Bypass Number Of Lines 1 to 3
Number of the UPS bypass phases
41
4x0041
Bypass Voltage Line 1
×10 Vac
Divide the value by 10 for real measurement:
2315/10=231.5 Vac
42
4x0042
Bypass Current Line 1
×10 A
Divide the value by 10 for real measurement:
21/10=2.1 A
44
4x0044
Bypass Voltage Line 2
×10 Vac
Divide the value by 10 for real measurement:
2315/10=231.5 Vac
45
4x0045
Bypass Current Line 2
×10 A
Divide the value by 10 for real measurement:
21/10=2.1 A
47
4x0047
Bypass Voltage Line 3
×10 Vac
Divide the value by 10 for real measurement:
2315/10=231.5 Vac
48
4x0048
Bypass Current Line 3
×10 A
Divide the value by 10 for real measurement:
21/10=2.1 A