background image

User Manual

UPSI-1208DP2

UPSI SYSTEM

DIN-RAIL

Bicker Elektronik GmbH

  

Ludwig-Auer-Straße 23

  

|

  

86609 Donauwörth · Germany

English

Содержание UPSI-1208DP2

Страница 1: ...User Manual UPSI 1208DP2 UPSI SYSTEM DIN RAIL Bicker Elektronik GmbH Ludwig Auer Straße 23 86609 Donauwörth Germany English ...

Страница 2: ...sion 0 1 Initial version 10 06 2020 Revision 1 Release version 03 07 2020 Revision 1 1 Chapter B2 extended Chapter B3 Environmental condition extended Chapter C1 Input data Internal input fuse changed Chapter C1 Environmental conditions extended 16 07 2020 Revision 1 2 PELV indication removed 09 11 2020 Revision 1 3 Chapter B3 Intended use more detailed specified Chapter C1 Environmental condition...

Страница 3: ...UPSI 1208DP2 Revision 1 3 3 ...

Страница 4: ... EDLC 3 5 kJ 0 972 Wh useful Ambient temperature Operating 20 65 C Storage Transport 30 65 C Operation altitude 4000 m Humidity 95 at 25 C no dew Dimensions W H D 63 x 120 x 100 mm 0 5 mm Weight 0 6 kg Technical Data UPSI 1208DP2 12 VDC 8 A A Brief specification 12V DC UPS DIN rail version Integrated maintenance free Supercaps Cycle Life 500000 Intelligent power sharing Regulatedoutputvoltageinbac...

Страница 5: ...re At very high or low temperatures a reduction of backup time occurs Unless otherwise specified the values apply to measurements at 25 C 0 20 40 60 80 100 120 140 160 180 200 220 240 260 280 300 320 10 15 20 25 30 35 40 45 50 55 60 65 70 75 80 85 90 95 100 Nominal backup time vs Pout Backup time sek Output Power W ...

Страница 6: ...tallation advice 17 E2 Convection and installation position 17 E3 Description of connectors 19 E4 Dimensioning the upstream power supply 20 E5 Initial operation 21 E6 Connecting diagram 22 E7 Overview connector Counterpart with part No Scope of delivery 23 E8 Charging time 23 E9 Reverse polarity Overload Short circuit 23 E10 Backup time 23 E11 Behavior in case of exceeding maximum backup time 24 E...

Страница 7: ...am source and also no voltage is measurable at the output the UPS can be still powered by the storage medium B3 Intended use Description This device is designed to be installed into a suitable enclosure which protects against electrical water and fire hazards and can then be used indoors and outdoors It is primary built for being mounted on a DIN Rail and is intended for professional use in applic...

Страница 8: ...devices into operation e g dents burn marks rough contamination 9 Keep ventilation openings clear 10 Do not drop the device 11 All parts of the device and accessories must not be eaten or swallowed 12 Use a current limited source for the UPS The required current values for the UPS are described in this manual 13 The UPS is powered by more than one source To shut down the UPS completely both the in...

Страница 9: ...gth max 18 VDC Fixed connect threshold Undervoltage Voltage drop Input Output 11 5 VDC 0 5 VDC max depending on load Current draw IN UN IOUT IN ICHARGE 0 IMAX UN IOUT ISTAT BOOST ICHARGE max INO LOAD UN IOUT 0 ICHARGE 0 ICHARGE UN IOUT 0 ICHARGE max 8 1 A 9 1 A 100 mA 3 5 A Power consumption PN UN IOUT IN ICHARGE 0 PMAX UN IOUT ISTAT BOOST ICHARGE max PCHARGE UN IOUT 0 ICHARGE max 97 2 W 109 2 W 4...

Страница 10: ...N ICHARGE 0 PSTAT BOOST UN IOUT ISTAT BOOST ICHARGE 0 PDYN BOOST UN IOUT IDYN BOOST ICHARGE 0 96 W 99 W n a Short circuit proof Yes No load proof Yes OUTPUT DATA UPSI 1208DP2 BACKUP MODE Unless otherwise stated all specifications apply to 25 C ambient temperature 12 V DC input voltage and nominal output current IN Output voltage 12 VDC Output voltage range n a Output current IN ISTAT BOOST IDYN BO...

Страница 11: ...r cross section with ferrule 0 129 mm 1 31 mm 26 16 AWG Stripping length 6 mm 7 mm Tightening torque 0 3 Nm 0 4 Nm ENERGY STORAGE UPSI 1208DP2 BP SUC 0835 Charging characteristic CC CV CP Nominal voltage UN 8 3 VDC End of charge voltage 8 3 VDC Charging current 15 5 A max Deep discharge protection 4 5 VDC Battery technology EDLC Nominal capacity 160 F useful 0 972 Wh or 3 5 kJ Charging time 2 min ...

Страница 12: ...beling RL Switch contact floating Relay Status configurable Power Fail Alarm State condition configurable Input voltage 22 5 VDC Switching voltage 24 VDC 125 VAC Current carrying capacity 1 A DC 0 5 A AC State signal assignment NO Normaly Open NC Normaly Closed configurable via Software Connection method Plug connection screwless Conductor cross section solid 0 205 mm 1 3 mm 24 16 AWG Conductor cr...

Страница 13: ...20 Protection class III without PE Mounting type DIN Rail mounting Housing version Aluminium Dimension W H D 63 mm 120 mm 100 mm 0 5 mm DATA INTERFACE RS232 Interface designation RS232 Numbers of interfaces 1 Connection method DSUB 9 Pin female Locking No Transmission physics RS232 light TX RX Topology Point to point Symbol rate baud rate 38400 Type of cable 1 1 Transmission length 10 m Access tim...

Страница 14: ...temperature operation 20 65 C Ambient temperature start up without load 30 C Ambient temperature storage transport 30 65 C Max permitted humidity 95 at 25 C no dew Installation height 4000 m Climate class 3k3 EN 60721 Degree of pollution 2 Indoor Outdoor use Yes Yes in housing ...

Страница 15: ...MHz 1 GHz 10 V m test level 3 1 4 GHz 2 GHz 3 V m test level 2 2 GHz 2 7 GHz 1 V m test level 1 Criterion A INTERFERENCE IMMUNITY ACCORDING TO EN 61000 6 2 INDUSTRY SECTOR Basic standard CE Normative minimum requirements EN 61000 6 2 CE Interference immunity of industrial environment Fast transients Burst EN 61000 4 4 Input Output Signal Comment 0 5 kV test level 1 symmetrical 0 5 kV test level 1 ...

Страница 16: ... impairment of the operating behavior that is corrected by the device itself C2 Drawing UPSI 1208DP2 120mm 63mm 9mm 44mm 100mm Tolerance 0 5 mm D Name Address Support E Mail Phone number of the manufacturer Bicker Elektronik GmbH Ludwig Auer Straße 23 86609 Donauwörth Germany E Mail support bicker de Tel 49 0 906 70595 0 ...

Страница 17: ...ges Pay attention to correct polarity Before commissioning check all the connections for correctness E2 Convection and installation position Do not cover any ventilation holes by adjacent components For this DIN rail versions vertical mounting on a horizontal rail DIN rails according to EN 60715 is recommended in order to achieve the best possible convec tion of the UPS Another mounting position i...

Страница 18: ...UPSI 1208DP2 Revision 1 3 18 DIN Rail mounting and DIN Rail profile according to EN 60715 2 3 4 1 Press down ...

Страница 19: ...n 2 Vin 3 Vout 4 Vout RS 232 PIN FUNCTION 1 NC 2 RXD 3 TXD 4 DTR 5 GND 6 DSR 7 NC 8 NC 9 NC RELAY CONNECTION RL Normally open contact NO When input power is interrupted the contact is closed 0Ω PIN FUNCTION 1 Relay contact 1 2 Relay contact 2 2 1 INPUT OUTPUT Vin Vout 4 3 2 1 ...

Страница 20: ...SELV or PELV power supply In order to operate the UPSI devices to the maximum the upstream power supply has to provide at least the following output currents and voltages For UPSI 1208DP2 10A 12V If less load than the maximum load is required at the output of the UPSI devices the voltage supply can be dimensioned according to the table below column 3 UPSI 1208DP2 ILOAD A ICHARGE A IIN MIN A 0 3 5 ...

Страница 21: ... at the input of the UPS is passed through to the output reduced by a current dependent voltage drop Vout Vin 0 5 V at maximum current The device charges the energy storage and monitors the upstream voltage thresholds at the input UPS function It must be ensured that the source supplies enough current to guarantee the charging process see also page 20 section E4 Dimensioning the upstream power sup...

Страница 22: ... Sub 9 RELAY VOUT USB RS232 RL STATUS IN OUT UPSI DC UPS 120 mm 63 mm m E6 Connection VIN VOUT ATTENTION 1 Note polarity 2 AWG18 wire should be used 1 mm2 CONNECTING ORDER 1 APPLICATION VOUT 2 DC SOURCE VIN 3 RELAY USB RS232 Dismantling order reverse to connection ...

Страница 23: ...n device off not active When the device is operating in backup mode reverse polarity protection not exists If the load current is too high for a duration longer than 3s the device switches off LED flashes quickly and continues oper ation automatically after 10s non latch In the event of a short circuit the output is immediately disconnected A start attempt is made every second non latch timer 1s T...

Страница 24: ...t and a lower voltage will appear at the output state 2s This condition should be avoided by shutting down the system in time before discharging the supercapacitors under high currents E12 Status LED 1 x flash pause 1 5s Status Battery start 2 x flash pause 1 5s Status Capacity for start is required state charging 3 x flash pause 1 5s Status shutdown Waiting for shutdown completion 4 x flash pause...

Страница 25: ...nd batteries should be placed within good air circulation The less deep the packs are discharged the longer the service life lasts E15 Maintenance The UPS contains no serviceable parts In case of a malfunction the upstream power source has to be discon nected and cables have to be removed Use a dry cloth for cleaning E16 Disposal Electric and electronic devices must not be disposed with domestic w...

Страница 26: ...ld be caused With maximum load the voltage at the input of the device must not undercut 11 5V Even after the upstream supply has been disconnected the device continues to run for some time after the shortfall of the load sensor setting of a threshold value for current currents below this value will be classified as system off no load A short direct at the output of the device can cause damage or d...

Страница 27: ...tions Windows is a registered trademark of the Microsoft Corp Status as at 09 11 2020 Revision 1 3 Bicker Elektronik GmbH Ludwig Auer Straße 23 86609 Donauwörth Germany Tel 49 0 906 70595 0 Fax 49 0 906 70595 55 E Mail info bicker de www bicker de ...