UPS for 480 Vac Grid, User Guide, doc. rel.4.0
Register
Variable name
GET Values
Remarks
50
4x0050
Temperature Alarm
0: Alarm off
1: Alarm on
61
4x0061
Ups General Fault Alarm 0: Alarm off
1: Alarm on
201
4x0201
System Model ID
1: Mega
PowerPlus
2: PowerPlus
Premium
3: UPS
4:
PowerPlusPrem
ium15
Future models
for units with
touch
controller will
be added.
202
4x0202
Model Nominal Power
kW
As defined by controller settings
203
4x0203
Maximum Amount of
Modules
As defined by controller settings or the
controller license
204
4x0204
Amount of Installed
Modules
As defined by controller settings, not the
actual responding modules
205
4x0205
Amount of Battery
Cabinets
As defined by controller settings
206
4x0206
Multisystem Mode
(Parallel Operation)
0: Stand alone
1: Multisystem
As defined by controller settings
207
4x0207
UPS On
0: UPS off
1: UPS on
208
4x0208
All Modules Are
Switched Off
0: All modules
are off
1: At least one
module is on
209
4x0209
Battery Status
0: Charging
1: Discharging
2: Low
3: Depleted
4: Fault
5: Test in
progress
6: Fully charged
Actual battery status as determined by
controller
210
4x0210
Seconds On Battery
Seconds
Only available during power failure, otherwise
zero
211
4x0211
Estimated Backup Time Minutes
Only available during power failure and when
the battery is fully charged (6 in 4x0209),
otherwise zero. This value is a rough
approximation received by mathematical
calculations, and assumes new and healthy