UPS for 480 Vac Grid, User Guide, doc. rel. 4.0
190
Register
Variable name
GET Values
Remarks
257
4x0257
Output Apparent Power
Line 1
×10 kVA
Divide the value by 10 for real measurement:
769/10=76.9 KVA
258
4x0258
Output Power Factor Line
1
0 to 100
Divide the value by 100 for real measurement:
87/100 = 0.87 PF
259
4x0259
Output Load Line 1
%
260
4x0260
Output Voltage Line 2
×10 Vac
Divide the value by 10 for real measurement:
2315/10=231.5 Vac
261
4x0261
Output Current Line 2
×10 A
Divide the value by 10 for real measurement:
21/10=2.1 A
262
4x0262
Output Power Line 2
×10 kW
Divide the value by 10 for real measurement:
453/10=45.3 KW
263
4x0263
Output Apparent Power
Line 2
×10 kVA
Divide the value by 10 for real measurement:
769/10=76.9 KVA
264
4x0264
Output Power Factor Line
2
0 to 100
Divide the value by 100 for real measurement:
87/100 = 0.87 PF
265
4x0265
Output Load Line 2
%
266
4x0266
Output Voltage Line 3
×10 Vac
Divide the value by 10 for real measurement:
2315/10=231.5 Vac
267
4x0267
Output Current Line 3
×10 A
Divide the value by 10 for real measurement:
21/10=2.1 A
268
4x0268
Output Power Line 3
×10 kW
Divide the value by 10 for real measurement:
453/10=45.3 KW
269
4x0269
Output Apparent Power
Line 3
×10 kVA
Divide the value by 10 for real measurement:
769/10=76.9 KVA
270
4x0270
Output Power Factor Line
3
0 to 100
Divide the value by 100 for real measurement:
87/100 = 0.87 PF
271
4x0271
Output Load Line 3
%
272
4x0272
Bypass Frequency
×10 Hz
Divide the value by 10 for real measurement:
502/10=50.2 Hz
273
4x0273
Bypass Voltage Line 1
×10 Vac
Divide the value by 10 for real measurement:
2315/10=231.5 Vac
274
4x0274
Bypass Current Line 1
×10 A
Divide the value by 10 for real measurement:
21/10=2.1 A
275
4x0275
Bypass Apparent Power
Line 1
×10 kVA
Divide the value by 10 for real measurement:
769/10=76.9 KVA
276
4x0276
Bypass Voltage Line 2
×10 Vac
Divide the value by 10 for real measurement:
2315/10=231.5 Vac
277
4x0277
Bypass Current Line 2
×10 A
Divide the value by 10 for real measurement:
21/10=2.1 A
278
4x0278
Bypass Apparent Power
Line 2
×10 kVA
Divide the value by 10 for real measurement:
769/10=76.9 KVA
279
4x0279
Bypass Voltage Line 3
×10 Vac
Divide the value by 10 for real measurement:
2315/10=231.5 Vac
280
4x0280
Bypass Current Line 3
×10 A
Divide the value by 10 for real measurement:
21/10=2.1 A
281
4x0281
Bypass Apparent Power
Line 3
×10 kVA
Divide the value by 10 for real measurement:
769/10=76.9 KVA