189
UPS for 480 Vac Grid, User Guide, doc. rel.4.0
Register
Variable name
GET Values
Remarks
234
4x0234
Charger Voltage Line 1 ×10 Vac
Divide the value by 10 for real measurement:
2315/10=231.5 Vac
235
4x0235
Charger Current Line 1
×10 A
Divide the value by 10 for real measurement:
21/10=2.1 A
236
4x0236
Charger Power Line 1
×10 kW
Divide the value by 10 for real measurement:
453/10=45.3 KW
237
4x0237
Charger Apparent Power
line 1
×10 kVA
Divide the value by 10 for real measurement:
769/10=76.9 KVA
238
4x0238
Charger Power factor
Line 1
0 to 100
Divide the value by 100 for real measurement:
87/100 = 0.87 PF
239
4x0239
Charger Load level Line 1 %
240
4x0240
Charger Voltage Line 2 ×10 V
Divide the value by 10 for real measurement:
2315/10=231.5 Vac
241
4x0241
Charger Current Line 2
×10 A
Divide the value by 10 for real measurement:
21/10=2.1 A
242
4x0242
Charger Power Line 2
×10 kW
Divide the value by 10 for real measurement:
453/10=45.3 KW
243
4x0243
Charger Apparent Power
line 2
×10 kVA
Divide the value by 10 for real measurement:
502/10=50.2 Hz
244
4x0244
Charger Power factor
Line 2
0 to 100
Divide the value by 100 for real measurement:
87/100 = 0.87 PF
245
4x0245
Charger Load level Line 2 %
246
4x0246
Charger Voltage Line 3 ×10 V
Divide the value by 10 for real measurement:
2315/10=231.5 Vac
247
4x0247
Charger Current Line 3
×10 A
Divide the value by 10 for real measurement:
21/10=2.1 A
248
4x0248
Charger Power Line 3
×10 kW
Divide the value by 10 for real measurement:
453/10=45.3 KW
249
4x0249
Charger Apparent Power
line 3
×10 kVA
Divide the value by 10 for real measurement:
502/10=50.2 Hz
250
4x0250
Charger Power factor
Line 3
0 to 100
Divide the value by 100 for real measurement:
87/100 = 0.87 PF
251
4x0251
Charger Load level Line 3 %
252
4x0252
Output Source
0: Normal
1: On Battery
2: On Bypass
3: Unknown
Unknown state can be shown when the
controller can't communicate with the ST/SW
module
253
4x0253
Output Frequency
×10 Hz
Divide the value by 10 for real measurement:
502/10=50.2 Hz
254
4x0254
Output Voltage Line 1
×10 Vac
Divide the value by 10 for real measurement:
2315/10=231.5 Vac
255
4x0255
Output Current Line 1
×10 A
Divide the value by 10 for real measurement:
21/10=2.1 A
256
4x0256
Output Power Line 1
×10 kW
Divide the value by 10 for real measurement:
453/10=45.3 KW