UPS for 480 Vac Grid, User Guide, doc. rel. 4.0
144
1.
From the System Menu select Operation > Turn on/off.
The Turn on/off screen appears:
Figure 129: Turn off/on menu
2.
Select System Off.
The Turning the system off will disconnect the load confirm dialog appears.
3.
Select OK.
The UPS is turned off.
8.3.2.
Operation > Turn On/Off > MODULES ON/OFF
8.3.2.1.
Operation > Turn on/off > MODULES OFF
Use this function to turn power modules OFF.
You can selectively turn off individual modules or all of them at once. And you can choose what
level of module shutdown to perform. Such as just Inverter off – per power module, or complete
shutdown of power modules.
If all modules are shut off the load is automatically transferred to bypass.
If the remaining power modules cannot support the remaining load, the load
will automatically be transferred to bypass (if you confirm).