UPS for 480 Vac Grid, User Guide, doc. rel. 4.0
188
Register
Variable name
GET Values
Remarks
batteries of average VRLA type in initial fully
charged state.
212
4x0212
Estimated Charge
0-100%
Mathematical calculation of battery charge in
percent; will send 200 if no value has been
calculated
213
4x0213
DC Voltage positive
×10 Vdc
Divide the value by 10 for real measurement:
2161/10=216.1 Vdc
214
4x0214
DC Voltage Negative
×10 Vdc
Divide the value by 10 for real measurement:
2161/10=216.1 Vdc
215
4x0215
DC Voltage total
×10 Vdc
Divide the value by 10 for real measurement:
8102/10=810.2 Vdc
216
4x0216
Battery Current
×10 A
Divide the value by 10 for real measurement:
21/10=2.1 A
217
4x0217
Battery Temperature
°C/°F
Degrees Centigrade/ Fahrenheit
218
4x0218
Number of phases
1 to 3
Number of the UPS phases (always 3 for
current units)
219
4x0219
Inverter Frequency Line 1 ×10 Hz
Divide the value by 10 for real measurement:
502/10=50.2 Hz
220
4x0220
Inverter Voltage Line 1
×10 Vac
Divide the value by 10 for real measurement:
2315/10=231.5 Vac
221
4x0221
Inverter Current Line 1
×10 A
Divide the value by 10 for real measurement:
21/10=2.1 A
222
4x0222
Inverter Power Line 1
×10 kW
Divide the value by 10 for real measurement:
453/10=45.3 KW
223
4x0223
Inverter Apparent Power
Line 1
×10 kVA
Divide the value by 10 for real measurement:
769/10=76.9 KVA
224
4x0224
Inverter Frequency Line 2 ×10 Hz
Divide the value by 10 for real measurement:
502/10=50.2 Hz
225
4x0225
Inverter Voltage Line 2
×10 Vac
Divide the value by 10 for real measurement:
2315/10=231.5 Vac
226
4x0226
Inverter Current Line 2
×10 A
Divide the value by 10 for real measurement:
21/10=2.1 A
227
4x0227
Inverter Power Line 2
×10 kW
Divide the value by 10 for real measurement:
453/10=45.3 KW
228
4x0228
Inverter Apparent Power
Line 2
×10 kVA
Divide the value by 10 for real measurement:
769/10=76.9 KVA
229
4x0229
Inverter Frequency Line 3 ×10 Hz
Divide the value by 10 for real measurement:
502/10=50.2 Hz
230
4x0230
Inverter Voltage Line 3
×10 Vac
Divide the value by 10 for real measurement:
2315/10=231.5 Vac
231
4x0231
Inverter Current Line 3
×10 A
Divide the value by 10 for real measurement:
21/10=2.1 A
232
4x0232
Inverter Power Line 3
×10 kW
Divide the value by 10 for real measurement:
453/10=45.3 KW
233
4x0233
Inverter Apparent Power
Line 3
×10 kVA
Divide the value by 10 for real measurement:
769/10=76.9 KVA