UPS for 480 Vac Grid, User Guide, doc. rel.4.0
8.2.5.4.
Setup > STSW > HIGH-LEVEL SETUP
These functions are related to the Static Switch.
Figure 85: Setup > STSW > High-level setup
Static Switch parameters should not be changed unless necessary.
8.2.5.4.1.
Setup > STSW > Hi-level setup > BYPASS FORCED/CONTROLLED
When the UPS wants to move to bypass mode, this function determines whether the controller
will check the quality of the bypass voltage or not, before moving to bypass.
Select Forced if you want the UPS to move to bypass regardless of the quality of the bypass
voltage.
Select Controlled if you want the UPS to determine if the bypass voltage is acceptable before
transferring to bypass. In this case, if the bypass voltage is not acceptable, the UPS remains in
Inverter mode. The range of what is an acceptable bypass voltage can be set to wide or
narrow.