UPS for 480 Vac Grid, User Guide, doc. rel. 4.0
58
To turn modules OFF, refer to Section 8.3.2.1. Start from the bottom (most)
module and work your way up.
Modules output current calibration should be performed only if necessary,
not casually.
Modules output current calibration should be performed only under
conditions where the input current is stable and not subject to fluctuation.
Calibration is best performed when the system is under relatively high
load (70+ %).
Auto Correction is enabled by default. This is the recommended setting for most
situations.
After performing any calibrations or adjustments the Auto Correction feature
should be re-enabled, for optimal system performance.
To perform power module output current calibration:
1.
Switch off all modules except for the bottom-most module.
2.
Go to Setup > Modules > Modules output current calibration.
The Modules output current calibration screen appears: