UPS for 480 Vac Grid, User Guide, doc. rel. 4.0
62
Figure 41: Dc voltage calibration
10.
Press the Confirm button to apply the corrected measurements.
11.
Switch OFF the module just calibrated and switch ON the next module above it.
12.
Perform steps 3 through 11 until all modules have been calibrated.
8.2.2.6.
AC OUTPUT VOLTAGE ADJUSTMENT
Use this function to modify the voltages of the individual output phases of a specific power
module.
The phase voltage can be adjusted upward or downward by up to 15 V.
Each power module’s output voltage phases are calibrated before the UPS leaves
the factory, but over time or due to environmental factors the UPS’s output
voltage may drift slightly.