107
UPS for 480 Vac Grid, User Guide, doc. rel.4.0
Figure 90: Setup > Alarms options
8.2.6.1.
Setup > Alarms > SET ALARM PRIORITIES
This function enables you to assign one of three possible levels of importance to each type of
system alarm. The levels of importance, in ascending order of importance, are Information,
Warning, and Critical.
Factory default settings are already assigned to each alarm message when you install the UPS. It
may be, however, that in your site an alarm condition is more (or less) important that the default
value assigned to the alarm. This function allows you to override the default value for a given
alarm.
You can scroll through all the possible alarm messages in the scroll box at the top of the window.
The assigned priority level for that alarm is highlighted. To modify the priority level, select the
desired button.
It is also possible to instruct the system to ignore a specific alarm, by pressing the Ignore button
(near the upper left corner of the screen).
8.2.6.2.
Setup > Alarms > ALARM LIMITS
This function lets you set the threshold values for several important alarms.