Protection
Protection Part Operation
SKF Multilog On
-Line System IMx-M
2 - 37
User Manual
Register "PRM CF Selftest" Bit Definition
Table 2-11: PRM CF Selftest bit definition.
Register "PRM CF - Selftest" Bit Definition**
Bit representation*
Description
(0x0000)
(No bit set)
Not used
0x0001
Selftest startup
0x0002
Selftest FW CRC
0x0004
Selftest configuration CRC
0x0008
S
elftest RAM RO
0x0010
Selftest CSTACK
0x0020
Selftest ISTACK
0x0040
Selftest RAM
0x0080
Selftest PSM
PRM CF Warning
Table 2-12: Protection module CF warning.
Protection Module CF Warning**
Bit representation
*
Condition
Comments
(0x0000)
(No bit set)
CF_WARNING_NONE
Normal. No errors.
0x0001
CF_WARNING_TEMP_ALER
T
Internal temperature of PRM is higher than 60
°
C
0x0002
CF_WARNING_TEMP_DANG
ER
Internal temperature of PRM is higher than 65
°
C
*
Important:
- Bit representation is in hexadecimal digits.
- Bit representation can be a combination of more than one condition.
Example:
Bit representation of 0x0003 is equal to 0x0001 CF_WARNING_TEMP
0x0002 CF_WARNING_TEMP_DANGER
Refer to Bit Representation of Combined Conditions.
Event Log chapter