Protection
Modbus
2 - 180
SKF Multilog O
n-Line System IMx-M
User Manual
Exported (Read) Modbus Registers
IMx-M item
Register
number(1)
Function
Data type
Min and Max
Digital Ch 1
Alarm
enable/disable
info
1729
See table Register
"Digital Ch Alarm
16-bit mask
-
↓
↓
Digital Ch 8
Alarm
enable/disable
info
1736
(1) Modbus register number 1 is equivalent to Modbus address 0x0000.
(2) Registers 609 to 622 must be read as one block, all at one single request.
(3) Registers 945 to 954 must be read as one block, all at one single request.
(4) For registers 609 to 622 when counter reaches its maximum value (65 535), the next incremental max value will
cause the counter to wrap to zero.
(5)
For registers 513 to 576 (Analog Sensor OK Max/Min) presented value is in mV except when measurement type
is configured as
Temperature.
For Temperature measurement, sensor OK limit is either in °C or °F presented
with one decimal. (Value is 10 times bigger than real value since last digit is the decimal value.)
MSB = Most Significant Bits
LSB = Least Significant Bits