Protection
Protection Module Configuration with IMx-M Manager
SKF Multilog On
-Line System IMx-M
2 - 95
User Manual
Figure 2 - 79.
Setting the IP Address by Using Hardware Switches.
•
It is required to set the first three part of the IP address of IP Settings
manually.
•
The last part of the IP address will be controlled by the HEX rotary switch
on IMx-M. For example, 10.0.0.1XY, where XY is derived from a
combination of the CMM + PRM slot number and the HEX rotary switch
position (see the table below).
Table 2-17: TCP/IP address/Slot ID when configured by HEX rotary switch.
HEX rotary
switch (x1)
TCP/IP address/Slot ID
CMM + PRM Slot
1
CMM + PRM Slot
2
CMM + PRM Slot
3
CMM + PRM Slot
4
0
1
2
3
↓
9
A
↓
F
Software defined
01
05
09
↓
33
37
↓
57
Software defined
02
06
10
↓
34
38
↓
58
Software defined
03
07
11
↓
35
39
↓
59
Software defined
04
08
12
↓
36
40
↓
60
Factory default configuration TCP/IP address: 10.0.0.1XY
•
These last two digits will also form the slot ID.
•
The HEX rotary switch has to be set manually.
•
The HEX rotary switch for IMx-M is located inside, back of the right-most
panel (looking at the rack from the front panel). In order to access it , first
turn off the power, then take the right-most panel out.
•
If the right-most slot has been mounted with a CMM + PRM pair, the CMM
must be dismounted first before the PRM due to the physical reason.
Otherwise, PRM can be damaged seriously. However, when mounting the