Protection
Protection Module Configuration with IMx-M Manager
2 - 120
SKF Multilog O
n-Line System IMx-M
User Manual
current status is normal. It will also inactivate any latching relays and first out
condition.
•
The configuration of latching sensor fault is set at each analog channel's sensor
configuration interface.
•
Configuration of latching relay is set at the general settings for relays as described
in Configuring a Relay Module chapter.
•
Slot Disarm
is to disarm the slot by using the digital input.
Important - If the configuration of a slot is to be updated and the slot is
disarmed through a digital input, it is strongly advised to make sure that the same
digital input is configured as slot disarm input. Failing to do so could lead to
unintentionally arming of the slot when the slot restarts and the new configuration
is activated.
•
Tripmultiply Input
activates the trip multiply setup entered at each analog channel
configuration interface for alert/danger settings on slot wise.
Slot trip multip
ly will activate/deactivate/override channel trip
multiply status.
•
The trip multiply status is stored in the backplane and will be recovered after a
power cycle or hot-swap procedure.
Once the digital channel type has been selected, the setup dialogue will
be refactored
based on the chosen type.
For the speed (or tachometer input) channel type, this will include additional fields to
support through the general and alarm levels settings.
For all other digital channel types (latching alarm reset, slot disarm and trip multiply
input), only the name and comment fields are required.