Protection
Protection Module Configuration with IMx-M Manager
SKF Multilog On
-Line System IMx-M
2 - 109
User Manual
Table 2-23: Valid filter selections for different measurement types.
Type
Filter
Temperature
DC
Radial shaft vibration
10
−
1 000 Hz,
5
−
1 000 Hz,
1
−
600 Hz,
4
−
4 000 Hz,
10
−
5 000 Hz
1
1 000
−
10 000 Hz
1
User defined
Position
DC
Complementary
differential expansion
DC
Piston rod drop (average mode)
-
Piston rod drop (triggered mode)
-
Casing vibration
10
−
1 000 Hz
1
−
600 Hz
4
−
4 000 Hz
2
5
−
1 000 Hz
10
−
5 000 Hz
1,2
1 000
−
10 000 Hz
1,2
User defined
Eccentricity
0
−
10 Hz
Other
DC
Gap
DC
1If this filter is activated, then only one channel of the pair can be used.
2This filter cannot be used if integration is selected.