Protection
Protection Module Configuration with IMx-M Manager
SKF Multilog On
-Line System IMx-M
2 - 117
User Manual
Figure 2 - 91.
Absolute Shaft Vibration Type Alarm Levels Setting.
•
Enter Time:
represent the period for a channel to have exceeded an alarm level
before an actual alarm condition is raised. Alert/Danger ON tr
igger will be delayed
by this Enter Time.
•
Trip Multiply Factor:
use this value to temporarily increase the already set alert
and danger levels. The entered factor must be between the values of 1 and 25,
with a single decimal being allowed (i.e. 1.5).
•
The activation of trip multiply at the slot is done via:
–
Digital channels interface by selecting the trip multiply input type
–
Local display selection keypad located on the front of condition monitoring
module
–
Modbus register 259 as described in
Imported (Write Single) Modbus Register
•
The activation of trip multiply at the channel level is done via:
–
Local display selection keypad located on the front of condition monitoring
module
–
Modbus register 260 as described in