Hardware
Installation
SKF Multilog On
-Line System IMx-M
4 - 5
User Manual
Figure 4 - 3.
Illustration of Desired Diverted Airflow.
One fan tray and an air guid
e plate shall be mounted for each IMx-M rack:
•
The fan tray must be mounted directly below each IMx-M rack.
•
The air guide plate must be mounted directly above each IMx-M rack.
The following cooling components are recommended:
•
Fan tray, article number: Rittal 3352.500
•
Guide frame, article number: Rittal 3357.100
•
Air guide plate, article number: Schroff 10713-144
When using the fan tray, the maximum allowed ambient operating temperature shall be
55 °C (
131 °F)
under normal operating conditions
Normal operating conditions are defined as all channels are
loaded with 17 mA each. For higher loads the maximum allowed
ambient temperature must be lowered.
Important: If CMM + PRM slot 4 is to be used, the maximum allowed ambient
temperature must not exceed 45 °C (113 °F).
For assembly and installation instructions of the fan tray, refer to the supplier's
documentation. It is important to ensure that the cables are secured in a proper way to
relieve the pressure from connectors.