Protection
Protection Module Configuration with IMx-M Manager
SKF Multilog On
-Line System IMx-M
2 - 161
User Manual
For alarm parameters for the combined measurement, only high alarms are
available because of the underlying mathematics which only produce results
equal to and greater than zero.
Figure 2 - 138.
Alarm Parameters for the Combined Measurement.
Configuring a Speed Digital Channel
To make the Piston rod drop measurement work in the selected mode the
associated digital channel MUST be configured for speed measurement.
When a digital channel is used together with Piston rod drop the “
Pulses per
rev.
” MUST be “1” and nothing else. If not “1” the Piston rod drop
measurements will not work correctly.