Protection
Protection Module Configuration with IMx-M Manager
2 - 136
SKF Multilog O
n-Line System IMx-M
User Manual
Configuration Examples
Absolute Shaft Vibration
Configuring a Casing Vibration Channel
Edit an analog channel setting by setting the
Type
to Casing vibration, the
Math Method
to Single integration, the Engineering Units (
EU
) to um, and the
Detection
type to Peak-to-Peak (PtP), P (true Peak) or RMS (true Root Mean
Averaging).
The channel selected must be one of a channel pair (i.e. If channel 3 is selected,
the shaft vibration channel must be channel 4, or if channel 6 is selected, the
shaft vibration channel must be channel 5).
Figure 2 - 105.
Initiating a Casing Vibration Analog Channel.
For this example, we will configure the casing vibration channel as shown in
the three figures below.