Hardware
Hardware Configuration
SKF Multilog On
-Line System IMx-M
4 - 21
User Manual
Digital Input Sensor Cables for Channels 5 to 8
Signal
Terminal
DIP B settings
Reset of latching
alert/danger.
Activation of trip multiply.
Activation of disarm.
N.C.
Shield
A
B
0
S
0100
N.C. = Not Connected
For the location of digital channel DIP switches, refer to
DIP Switches on Protection Module
Speed/Tacho - Minimum Pulse Widths
Figure 4 - 12.
Minimum Pulse
W
idth for an Electrical Positive Tacho Signal.
Figure 4 - 13.
Minimum Pulse
W
idth for an Electrical Negative Tacho Signal.
Buffered Outputs
Back Side Buffered Outputs
On the back of each CMM + PRM slot there are 16 buffered analog outputs
marked as "Buf A" and 8 buffered digital outputs marked as "Buf D" as shown
in Protection Module (PRM)Protection Module (PRM)Protection Module
(PRM)Protection Module (PRM)Protection Module (PRM)Protection Module
(PRM)Protection Module (PRM)Protection Module (PRM).
•
The buffered analog signal is divided by 2.
The measuring instrument connected to these buffered outputs must
compensate for this. This can be done by using a sensitivity that is 50% of the
connected sensor. For example, if the sensor is 100 mV/g, then set the
sensitivity on the measuring instrument to 50 mV/
g.
•
The buffered analog outputs are maximum ±11 V and cutoff frequency (-3
dB) is at 60 kHz
•
The buffered digital outputs are 5 V TTL signal.