Protection
Modbus
2 - 178
SKF Multilog O
n-Line System IMx-M
User Manual
Exported (Read) Modbus Registers
IMx-M item
Register
number(1)
Function
Data type
Min and Max
Comb 1 Alert
Low
1329
Combined Ch 1 Alert
Low trigg level
Signed 16 bits
-32 768 to
+32 767 (see also
corresponding Combined
ch Alert/Danger Trigg
Scale)
↓
↓
↓
Comb 8 Alert
Low
1336
Combined Ch 8 Alert
Low trigg level
Comb 1 Alert
High
1337
Combined Ch 1 Alert
High trigg level
Signed 16 bits
-32 768 to
+32 767 (see also
corresponding Combined
ch Alert/Danger Trigg
Scale)
↓
↓
↓
Comb 8 Alert
High
1344
Combined Ch 8 Alert
High trigg level
Comb 1 Danger
Low
1377
Combined Ch 1
Danger Low trigg level
Signed 16 bits
-32 768 to
+32 767 (see also
corresponding Combined
ch Alert/Danger Trigg
Scale)
↓
↓
↓
Comb 8 Danger
Low
1384
Combined Ch 8
Danger Low trigg level
Comb 1 Danger
High
1385
Combined Ch 1
Danger High trigg
level
Signed 16 bits
-32 768 to
+32 767 (see also
corresponding Combined
ch Alert/Danger Trigg
Scale)
↓
↓
↓
Comb 8 Danger
High
1392
Combined Ch 8
Danger High trigg
level
Comb 1 Trip
Multiply Factor
1425
See table Analog Ch
Trip Multiply Factor
Definition
16-bit mask
-
↓
↓
Comb 8 Trip
Multiply Factor
1432
Comb 1 Ch
Status
1433
See table Register
"Analog Ch Status" Bit
Definition
16-bit mask
-
↓
↓
Comb 8 Ch
Status
1440