Technical Data
Analog Measurement - Protection
SKF Multilog On
-Line System IMx-M
7 - 3
User Manual
•
Up to 96 configurable relay outputs (Disarm, Alert, Danger, No
t OK and Voting)
•
Slot status circuit fault (CF) relay output
•
Slot disarm (Dis) relay output
Analog Measurement - Protection
•
16-
bit AD conversion enabling continuous transient capture (no gain or AC/DC
switching required)
•
True simultaneous sampling of all 64 channels (no multiplexing)
•
Simultaneous sampling of different channels with different sampling rates
•
Frequency range: from DC to 10 kHz
•
Dynamic range: 90 dB
•
Signal to noise ratio: 90 dB
•
Cross-talk rejection: 100 dB
•
Accuracy amplitude: ±2% (Velocity 1 000 to 10 000 Hz, ±3%)
Typical accuracy amplitude < ±1% of API 670 defined full scale range.
Note
: Filters ±0,5 dB in passband
•
Accur
acy measurement type Other:
±1% for 0-10 VDC input
±2,9% for 4-20 mA input
Note
: Accuracy ±1% (±2,9% for 4-20 mA) is only fulfilled if the complete 0-10 V or
complete 4-20 mA range is utilized to reflect the configured full scale.
Digital Measurement – Protection
•
Frequency range: 0,1 Hz to 7,5 kHz (Eddy current probe low frequency limit 2 Hz)
•
Required pulse width: > 25 µs for electrical positive, > 67 µs for electrical negative
•
Accuracy frequency: 0,05% of measurement value (typically 0,01% up to 2,5 kHz)
•
Peak speed detection
Relay - Protection
•
Maximum switching voltage: up to 60 V DC, 30 V RMS/42,4 V peak
•
Maximum switching capacity: 60 W, 62,5 VA
•
Maximum switching current: max 2 A peak, max 1 A continuously
•
Mechanical endurance: typical 10
8
operations
•
Electrical endurance: minimum 10
5
operations at maximum rating
•
Category of protection: hermetically sealed (RT V)