Protection
Modbus
2 - 174
SKF Multilog O
n-Line System IMx-M
User Manual
Exported (Read) Modbus Registers
IMx-M item
Register
number(1)
Function
Data type
Min and Max
Dig Ch 1 Peak
RPM
74
Digital Ch 1 Peak
Speed
Unsigned 16 bits
0 to 65 535
↓
↓
↓
Dig Ch 8 Peak
RPM
81
Digital Ch 8 Peak
Speed
Dig Ch 1 Status
82
See table Register
"Digital Ch Status" Bit
Definition
16-bit mask
-
↓
↓
Dig Ch 8 Status
89
System
Status 2
257
See table Protection
Module Circuit Faults
- PRM-M
16-bit mask
-
Analog Ch 1
Sensor OK Max
Trigg level
513
Analog Ch 1 Sensor
OK max trigg level
(5)
Signed 16 bits
-32 768 to
+32 767
↓
↓
↓
Analog Ch 16
Sensor OK Max
Trigg level
528
Analog Ch 16 Sensor
OK max trigg level
(5)
Analog Ch 1
Sensor OK Min
Trigg level
561
Analog Ch 1 Sensor
OK min trigg level
(5)
Signed 16 bits
-32 768 to
+32 767
↓
↓
↓
Analog Ch 16
Sensor OK Min
Trigg level
576
Analog Ch 16 Sensor
OK min trigg level
(5)
Modbus L1
Statistics(2)
609
Number of Short
frame errors
Unsigned 16 bits
0 to 65 535(4)
610
Number of Long
frame errors
611
Number of CRC errors
612
Number sent
613
Number received
614
Number of Rx timeout
errors
615
Number of Uart
errors