![Siemens SIWAREX WP251 Скачать руководство пользователя страница 62](http://html.mh-extra.com/html/siemens/siwarex-wp251/siwarex-wp251_manual_374538062.webp)
Scale parameters and functions
8.3 DR 3 Calibration parameters
SIWAREX WP251
62
Manual, 12/2015, A5E37203357A
Basic calibration of the scale is accomplished through the calibration parameters and
calibration procedure (assignment of zero point and reference point). With a wire jumper on
the "P" and "PR" terminals (parameter protection), most of DR 3 parameters can no longer
be changed (write-protected). This provision is relevant for applications requiring official
calibration. All changes in data record 3 require service mode to be switched on for the
module. If service mode is not active, all parameter inputs are directly rejected with an error.
Procedure
●
Read DR 3 from SIWAREX (in SIWATOOL, SIMATIC DB or ModbusMaster)
●
Check all parameters and change them for the specific application
●
Transfer data record DR 3 to SIWAREX (from SIWATOOL, SIMATIC DB or Modbus
Master)
●
Perform the calibration of the scale (zero point and calibration point 1 – optionally
calibration point 2)
●
Read DR 3 from SIWAREX (in SIWATOOL, SIMATIC DB or ModbusMaster)
Table 8- 1
Assignment of data record 3
Parameter
Description
Format
Length
[bytes]
De-
fault
Min
Max
Write
protec-
tion
Modbus
holding
register
Data record number
Contains no. of the
data record
USHORT
2
3
-
-
-
1000
Length
Data record length
information
USHORT
2
172
-
-
-
1001
Application
Information on appli-
cation to which DR
belongs
USHORT
2
105
-
-
-
1002
Version identifier
Current data record
version information
USHORT
2
1
1
65535
-
1003
Scale name header
Maximum length and
actual length of string
for scale name
UBYTE
2
12,
12
-
-
x
1004
Scale name (Page 66)
Freely selectable
scale name
CHAR
12
" "
-
-
x
1005
Unit of weight (Page 66) 0: "mg"
1: "g"
2: "kg"
3: "t"
4: "oz" (ounce)
5: "lb" (pound)
6: "T" (=short tons)
7: "TL" (= long tons)
USHORT 2
2
0
6
x
1011
Gross identifier (Page 66) 0: "B"
1: "G"
USHORT 2
0
0
1
x
1012
(Page 67)
0: None
1: OIML
USHORT 2
0
-
-
-
1013
Reserve
Reserve
USHORT 2
0
-
-
-
1014
Содержание SIWAREX WP251
Страница 28: ...Mounting 5 3 Mounting on the SIMATIC S7 1200 SIWAREX WP251 28 Manual 12 2015 A5E37203357A ...
Страница 40: ...Connection 6 12 Attachment of calibration protection plate SIWAREX WP251 40 Manual 12 2015 A5E37203357A ...
Страница 56: ...Commissioning 7 5 Service with the SIWATOOL program SIWAREX WP251 56 Manual 12 2015 A5E37203357A ...
Страница 162: ...Scale parameters and functions 8 38 DR 48 date and time 2 for Modbus SIWAREX WP251 162 Manual 12 2015 A5E37203357A ...
Страница 212: ...Technical specifications 13 3 Approvals SIWAREX WP251 212 Manual 12 2015 A5E37203357A ...
Страница 218: ...List of abbreviations B 1 List of abbreviations SIWAREX WP251 218 Manual 12 2015 A5E37203357A ...