![Siemens SIWAREX WP251 Скачать руководство пользователя страница 169](http://html.mh-extra.com/html/siemens/siwarex-wp251/siwarex-wp251_manual_374538169.webp)
Errors and messages
9.6 Operating errors
SIWAREX WP251
Manual, 12/2015, A5E37203357A
169
Data and command errors Error code Additional
string
Description
6056 Memory command
error
6056
Trace, logging or logbook command was rejected. Additional
information contains details.
4500
, because a fault is present
4501
, because no standstill occurred
4502
, because module is already waiting for standstill
4511
, because write protection active
4532
, because weight is outside the permissible weighing range
4550
, because trace memory full
4551
, because log memory full
4552
, because memory task busy
7050 Unknown data record 7050
-
Requested data record is unknown.
7051 Parameter input not
possible now
7051
A parameter input is currently not possible. Additional information
contains details.
4507
, because dosing active
4510
, because service mode is not active
4511
, because write protection active
3519
, because password incorrect
7052 Parameter is write
protected and cannot be
changed
7052
A parameter input is currently not possible due to active write
protection. Additional information contains details about the pa-
rameter involved.
Parameter
ID
Parameter ID of the parameter involved
7053 Error in calibration
parameter DR 3
7053
Additional information indicates an implausible parameter in DR 3
Parameter
ID
Parameter ID of the affected parameter in DR 3
4510
, because service mode is not active
4520
, because increment between calibration digits is too small
4521
, because order of calibration points is incorrect
4524
, because calibration weight 0
4525
, because falling characteristic curve not allowed by OIML
4526
, because mixed characteristic curve not allowed
4610
, because weighing range max - min error
4611
, because resolution not permitted
4613
, because OIML and 3000d requirements violated
7054 Parameter error DR 5 7054
Additional information indicates an implausible parameter in DR 5
Parameter
ID
Parameter ID of the affected parameter in DR 5
Содержание SIWAREX WP251
Страница 28: ...Mounting 5 3 Mounting on the SIMATIC S7 1200 SIWAREX WP251 28 Manual 12 2015 A5E37203357A ...
Страница 40: ...Connection 6 12 Attachment of calibration protection plate SIWAREX WP251 40 Manual 12 2015 A5E37203357A ...
Страница 56: ...Commissioning 7 5 Service with the SIWATOOL program SIWAREX WP251 56 Manual 12 2015 A5E37203357A ...
Страница 162: ...Scale parameters and functions 8 38 DR 48 date and time 2 for Modbus SIWAREX WP251 162 Manual 12 2015 A5E37203357A ...
Страница 212: ...Technical specifications 13 3 Approvals SIWAREX WP251 212 Manual 12 2015 A5E37203357A ...
Страница 218: ...List of abbreviations B 1 List of abbreviations SIWAREX WP251 218 Manual 12 2015 A5E37203357A ...