Errors and messages
9.3 Evaluating errors/messages with the help of SIWATOOL
SIWAREX WP251
164
Manual, 12/2015, A5E37203357A
9.3
Evaluating errors/messages with the help of SIWATOOL
The electronic weighing system has a message buffer that stores the last 80 entries
including time stamp in non-volatile memory. If the number of messages in the message
buffer exceeds 80, the oldest entry is overwritten. The message buffer can be read out at
any time with the help of SIWATOOL (menu item "Read out all data records") and saved
together with the scale parameters. This facilitates the detection, analysis and correction of
errors in the system. The only way to completely clear the message buffer is with the "Load
factory settings" command.
9.4
Evaluating errors/messages with the help of the function block
The electronic weighing system has a message buffer that stores the last 80 entries
including time stamp in non-volatile memory. If the number of messages in the message
buffer exceeds 80, the oldest entry is overwritten. The message buffer can be read out at
any time with the help of SIWATOOL (menu item "Read out all data records") and saved
together with the scale parameters. This facilitates the detection, analysis and correction of
errors in the system. The only way to completely clear the message buffer is with the "Load
factory settings" command.
9.5
Evaluating errors/messages using Modbus
Data record DR 32 is available for detecting and evaluating errors/messages using Modbus
(see DR 32 Error messages (Page 145)). This is updated automatically by SIWAREX and
contains a bit for each message that is set for 3 seconds when an error occurs. Thus, the
registers can be read directly by a Modbus master and the individual bits can be monitored.
In addition to the error bits, there is additional information with further details on the cause of
the error.
9.6
Operating errors
9.6.1
Operating errors
Operating errors
Error
code
Description and remedy
1000 operating error exists
1000
Group message, there is at least one operating error.
1001 Watchdog
1001
Watchdog error. A critical error has occurred in the function of the module.
Contact SIWAREX Support if the error recurs.
Reserve
Reserve Reserve
1003 Checksum error (parame-
ters)
1003
The checksum of the parameters no longer matches. Remedy: Load factory
settings. Contact SIWAREX Support if the error recurs.
Содержание SIWAREX WP251
Страница 28: ...Mounting 5 3 Mounting on the SIMATIC S7 1200 SIWAREX WP251 28 Manual 12 2015 A5E37203357A ...
Страница 40: ...Connection 6 12 Attachment of calibration protection plate SIWAREX WP251 40 Manual 12 2015 A5E37203357A ...
Страница 56: ...Commissioning 7 5 Service with the SIWATOOL program SIWAREX WP251 56 Manual 12 2015 A5E37203357A ...
Страница 162: ...Scale parameters and functions 8 38 DR 48 date and time 2 for Modbus SIWAREX WP251 162 Manual 12 2015 A5E37203357A ...
Страница 212: ...Technical specifications 13 3 Approvals SIWAREX WP251 212 Manual 12 2015 A5E37203357A ...
Страница 218: ...List of abbreviations B 1 List of abbreviations SIWAREX WP251 218 Manual 12 2015 A5E37203357A ...