Scale parameters and functions
8.18 DR18 Control digital outputs
SIWAREX WP251
Manual, 12/2015, A5E37203357A
107
8.18
DR18 Control digital outputs
8.18.1
Overview
If one or more digital outputs were defined in data record DR 7 for controlling using data
record DR 18 (see Assignment of digital output DQ.0, DQ.1, DQ.2, DQ.3 (Page 91)), this
output can be controlled using data record DR 18. Only outputs that were configured for
controlling using DR 18 (see Overview (Page 86)) are controlled based on the content of
data record DR 18. The set values are not saved in non-volatile memory!
In addition, transitions for the individual weighing steps 0 to 7 can be set in DR 18. With a set
(=TRUE) transition, the respective weighing step is not executed until the corresponding
transition is reset from TRUE to FALSE. The transitions are not saved in non-volatile
memory!
Procedure
●
Check or adapt the desired parameter settings of the digital outputs in data record 7
●
Specify the value for digital output DQ.0, DQ.1, DQ.2, DQ.3
●
Transfer the data record to the scales
Table 8- 18 Assignment of data record 18
Variable
Note
Type
Length
(bytes)
Rw
De-
fault
Min. Max. Modbus
registers
Data record
number
Contains no. of the data record
USHORT
2
r
18
-
-
1616
Length
Data record length information
USHORT
2
r
12
-
-
1617
Application
Information about which application the DR
belongs to
USHORT
2
r
105
-
-
1618
Version
identifier
Current data record version information
USHORT
2
r
1
1
65635
1619
(Page 108)
Specification for digital output 0=1
→ DQ.0
output active
(only applies if output is assigned function
code 64, see DR 7)
BIT
0
rw
0
0
1
1620.16
Specification for digital output 1=1 → DQ.1
output active
(only applies if output is assigned function
code 64, see DR 7)
BIT
0
rw
0
0
1
1620.15
Specification for digital output 2=1 → DQ.2
output active
(only applies if output is assigned function
code 64, see DR 7)
BIT
0
rw
0
0
1
1620.14
Specification for digital output 3=1 → DQ.3
output active
(only applies if output is assigned function
code 64, see DR 7)
BIT
0
rw
0
0
1
1620.13
Reserve
Reserve
BIT
0
rw
0
0
1
1620.12
Содержание SIWAREX WP251
Страница 28: ...Mounting 5 3 Mounting on the SIMATIC S7 1200 SIWAREX WP251 28 Manual 12 2015 A5E37203357A ...
Страница 40: ...Connection 6 12 Attachment of calibration protection plate SIWAREX WP251 40 Manual 12 2015 A5E37203357A ...
Страница 56: ...Commissioning 7 5 Service with the SIWATOOL program SIWAREX WP251 56 Manual 12 2015 A5E37203357A ...
Страница 162: ...Scale parameters and functions 8 38 DR 48 date and time 2 for Modbus SIWAREX WP251 162 Manual 12 2015 A5E37203357A ...
Страница 212: ...Technical specifications 13 3 Approvals SIWAREX WP251 212 Manual 12 2015 A5E37203357A ...
Страница 218: ...List of abbreviations B 1 List of abbreviations SIWAREX WP251 218 Manual 12 2015 A5E37203357A ...