Communication
2.1 PROFIBUS communication
SIMOCODE pro - Communication
Function Manual, 11/2018, A5E40508495002A/RS-AC/003
25
Channel-related diagnostics - definition
Channel-related diagnostics is a detailed version of the identifier-related diagnostics. It
supplies information about the device faults of SIMOCODE pro.
Channel-related diagnostics - configuration
Channel-related diagnostics is configured as follows:
Figure 2-7
Configuration of the channel-related diagnostics
The block for the channel-related diagnostics, which has a length of 3 bytes, is either missing
(if there is no channel-related diagnostics) or is available once or twice.
Fault types
The diagnostic message is output on channel 0.
Table 2- 7
Fault types
No.
Fault type
Meaning / cause
F9
01001: Error
•
Internal fault / device fault
•
Error during self-test
Precise information:
See Chapter Data record 92 -
Device diagnostics (Page 165).
F16
10000: Parameterization error
•
Incorrect parameter value