Communication
2.2 PROFINET communication
SIMOCODE pro - Communication
76
Function Manual, 11/2018, A5E40508495002A/RS-AC/003
Example of the diagnostics data records
The following example shows the content of the data record 0xC010 with the pending fault
"execution of ON command":
Table 2- 27 Content of data record 0xC010 for the pending fault "execution ON command"
BlockType
0x0010: Diagnostics data record
BlockLength
0x0016: Block length 22 bytes
BlockVersion
0x0101: always 0x0101 in the case of SIMOCODE
API
0x00000000: always 0 in the case of SIMOCODE
SlotNumber
0x0001: Slot 1 - I/O address
SubslotNumber
0x0001: Sub-slot 1
ChannelNumber
0x8000: Submodule
ChannelProperties
0x0800: Pending diagnostics
USI (User Structure Identifier)
0x8000: Channel diagnostics
ChannelNumber
0x0000: always 0 in the case of SIMOCODE
ChannelProperties
0x6804: Pending diagnostics
ChannelErrorType
0x1000: Execution ON command