Tables, data records
3.4 Tables, PROFINET data records
SIMOCODE pro - Communication
Function Manual, 11/2018, A5E40508495002A/RS-AC/003
247
Byte.
Bit
Designation (PRM group)
Type Range
Unit
Default Note
Information
48.0 Truth table 1 type 3I/1O
Byte 0 -
11111111
B
0
49.0 Truth table 2 type 3I/1O
Byte 0 -
11111111
B
0
50.0 Truth table 3 type 3I/1O
Byte 0 -
11111111
B
0
51.0
Reserved
Byte
0
52.0 Word parameters (32)
52.0 Motor protection - Cooling down
period
Word 600 -
65535
100
ms
3000
IM UM(+)
54.0 Motor protection - Pause time
Word 0 - 65535 100
ms
0
0 = disabled
IM UM(+)
56.0 Execution time
Word 0 - 65535 100
ms
10
0 = disabled
58.0 Monitoring the number of starts
- Time range for starts
Word 0 - 65535 1 s
0
60.0 Monitoring the number of starts
- Interlocking time
Word 0 - 65535 1 s
0
62.0 Motor stop time level >
Word 0 - 65535 1 h
0
64.0 Timer 1 - Limit
Word 0 - 65535 100
ms
0
66.0 Timer 2 - Limit
Word 0 - 65535 100
ms
0
68.0 Counter 1 - Limit
Word 0 - 65535
0
70.0 Counter 2 - Limit
Word 0 - 65535
0
72.0 EM+
2)
- trip level
Word 30 -
40000
1 mA 1000
74.0 EM+
2)
- warning level
Word 30 -
40000
1 mA 500
76.0 D-word parameters (36)
76.0 Operator control enables
Bit
[32]
0 - 1-1B
0-0B
80.0 Motor protection - Set current
I
s
1
D-
word
1)
10
m
A
30
IM UM(+)
84.0 Motor operating hours level >
D-
word
0 -
0xFFFFF
FFF
1 s
0
88.0
Reserved
D-
word
0
1) Value range dependent on current range of the IM / UM and the conversion factor
Bit 31 = 1, i.e. conversion factor active.
2) 3UF7510-1AA00-0 ground-fault module