Tables, data records
3.4 Tables, PROFINET data records
SIMOCODE pro - Communication
Function Manual, 11/2018, A5E40508495002A/RS-AC/003
253
Byte.Bit
Designation (PRM group)
Type
Range
Unit
Default
Note
Info
7.4
Monitoring external fault 5
Bit
0, 1
0
0 = Always
1 = Only motor ON
7.5
Monitoring external fault 6
Bit
0, 1
0
7.6
Reserved
Bit
0
7.7
Reserved
Bit
0
8.0
Calculator 2, Operating
mode
Bit
0, 1
0
0 = Word
1 = D-word
8.1
Reserved
Bit
0
8.2
DM-F - Safe tripping function Bit
0, 1
0
0 = No
1 = Yes
DM-F
8.3
DM-F - Safety-related
tripping reset
Bit
0, 1
0
0 = Manual
1 = Auto
DM-F
8.4
Reserved
8.5
Reserved
Bit
0
8.6
Reserved
Bit
0
8.7
Reserved
Bit
0
9.0
DM-FL - Configuration 1
Bit
0, 1
0
Configurable
parameters
comparable with the
module
configuration
DM-FL
9.1
DM-FL - Configuration 2
Bit
0, 1
0
DM-FL
9.2
DM-FL - Configuration 3
Bit
0, 1
0
DM-FL
9.3
DM-FL - Configuration 4
Bit
0, 1
0
DM-FL
9.4
DM-FL - Configuration 5
Bit
0, 1
0
DM-FL
9.5
DM-FL - Configuration 6
Bit
0, 1
0
DM-FL
9.6
DM-FL - Configuration 7
Bit
0, 1
0
DM-FL
9.7
DM-FL - Configuration 8
Bit
0, 1
0
DM-FL
10.0
Bit[2] - Parameters (21)
10.0
Reserved
Bit[2]
10.2
Reserved
Bit[2]
0
10.4
UVO timebase
Bit[2]
0, 1, 2
0
10.6
UVO operating mode
Bit[2]
0, 1, 2
0
0 = Deactivated
1 = Activated
11.0
Trip monitoring U<
Bit[2]
0, 1, 2
1
0 = ON (always)
1 = ON+ (always,
not TPF)
2 = RUN (motor ON,
not TPF)
UM(+)
11.2
Warning monitoring U<
Bit[2]
0, 1, 2
1
UM(+)
11.4
Reserved
Bit[2]
0
11.6
Reserved
Bit[2]
0
12.0
Trip monitoring 0/4-20 mA> Bit[2]
0, 1, 2, 3
0
0 = ON (always)
1 = ON + (always,
not TPF)
2 = RUN (motor ON,
not TPF)
3 = RUN+ (motor
ON, not TPF,
AM1
12.2
Warning monitoring 0/
4-20 mA>
Bit[2]
0, 1, 2, 3
0
AM1
12.4
Trip monitoring 0/4-20 mA< Bit[2]
0, 1, 2, 3
0
AM1
12.6
Warning monitoring 0/4-20
mA<
Bit[2]
0, 1, 2, 3
0
AM1
13.0
Monitoring limit 1
Bit[2]
0, 1, 2, 3
0