Tables, data records
3.4 Tables, PROFINET data records
SIMOCODE pro - Communication
236
Function Manual, 11/2018, A5E40508495002A/RS-AC/003
Byte.Bit Designation
Information
PNIO
diagnostic
status **)
PNIO error
number (channel
error type)
Error no.
29.5
Reserved bit[3]
30.0
Faults -
Miscellaneous
Fault - External fault 1
3
0x1070
56
30.1
Fault - External fault 2
3
0x1071
57
30.2
Fault - External fault 3
3
0x1072
58
30.3
Fault - External fault 4
3
0x1073
59
30.4
Fault - External fault 5
3
0x1074
60
30.5
Fault - External fault 6
3
0x1075
61
30.6
Fault - Dry running pump
3
0x104D
62
30.7
Fault - Underfill protection -
Fault
3
0x104E
63
31.0
Fault - AM1 open circuit
AM1
3
0x105B
64
31.1
Fault - Test trip
3
0x1055
65
31.2
Fault - DM-F safety-related
tripping
DM-F
3
0x0019
66
31.3
Fault - DM-F wiring
DM-FL
3
0x1061
67
31.4
Fault - DM-FL cross circuit
DM-FL
3
0x1062
68
31.5
Reserved bit[3]
32.0
Faults -
Protection
extended
Fault - TM2 trip T >
TM2
3
0x102E
32.1
Fault - TM2 sensor fault
TM2
3
0x102F
32.2
Fault - TM2 out of range
TM2
3
0x1030
32.3
Reserved bit[5]
33.0
Faults - Level
monitoring
extended
Fault - Trip 0/4-20mA >
AM2
3
0x104A
33.1
Fault - Trip 0/4-20mA <
AM2
3
0x104B
33.2
Reserved bit[6]
34.0
Faults -
Miscellaneous
extended
Fault - AM2 open circuit
AM2
3
0x105C
34.1
Reserved bit[7]
35.0
Reserved bit[8]
36.0
Warnings -
Protection
extended
Warning - TM2 warning T >
TM2
2
0x102E
36.1
Reserved
36.2
Warning - TM2 sensor fault
TM2
2
0x102F
36.3
Warning - TM2 out of range
TM2
2
0x1030
36.4
Reserved bit[4]