Communication
2.2 PROFINET communication
SIMOCODE pro - Communication
74
Function Manual, 11/2018, A5E40508495002A/RS-AC/003
Data block "ChannelErrorType"
The ChannelErrorType does not indicate the "Fault" status. For this purpose, there is the
PNIO diagnostics status for the raised alarm: Maintenance Required, Maintenance
Demanded, Failure.
Table 2- 25 ChannelErrorType
ChannelErrorType Meaning
0x0009
Error
1)
0x0010
Parameterization error
1)
Error of the PROFINET interface
0x8000
Data transmission not possible
0x8001
Incorrect neighborhood
0x8002
Loss of redundancy
0x8003
Loss of synchronization (bus end)
0x8004
Loss of clock synchronization (device end)
0x8005
Slave-to-slave traffic connection error
0x8008
Error in network component
0x8009
Timebase error
Device diagnostics
0x1000
Execution ON command
0x1001
Execution stop command
0x1002
Feedback (FB) ON
0x1003
Feedback (FB) OFF
0x1004
Stalled positioner
0x1005
Double 0
0x1006
Double 1
0x1007
End position
0x1008
Antivalence
0x100A
Cold start (TPF)
0x100B
Power failure (UVO)
0x100C
Operational protection OFF (OPO)
0x1021
Unbalance
0x1022
Overload
0x1023
Ov Loss of phase
0x1024
Thermistor overload
0x1025
Thermistor short circuit
0x1026
Thermistor open circuit
0x1027
Internal ground fault
0x1028
EM/EM+ External ground fault
0x1029
EM+ open circuit
0x1030
TM2 out of range
0x102A
EM+ short circuit
0x102B
TM1 trip level T>