Tables, data records
3.1 Tables general
SIMOCODE pro - Communication
126
Function Manual, 11/2018, A5E40508495002A/RS-AC/003
Table 3- 2
Contactor control with control functions
Designation / control function
Contactor control
QE1
QE2
QE3
QE4
QE5
Overload
1) 2) 3)
-
-
Active
-
-
Direct-on-line starter
1) 2) 3)
ON
-
-
-
-
Reversing starter
1) 2) 3)
CW
CCW
-
-
-
Circuit breaker
1) 2) 3)
ON pulse
-
OFF pulse
-
-
Star-delta starter
2) 3)
Star contactor Delta contactor Line contactor
-
-
Star-delta reversing starter
3)
Star contactor Delta contactor RIGHT line
contactor
LEFT line
contactor
-
Dahlander starter
3)
FAST
SLOW
Star contactor
FAST
-
-
Dahlander reversing starter
3)
CW-FAST
CW-SLOW
Star contactor
FAST
CCW-SLOW CCW-FAST
Pole-changing starter
3)
FAST
SLOW
-
-
-
Pole-changing reversing starter
3)
CW-FAST
CW-SLOW
-
CCW-SLOW CCW-FAST
Solenoid valve
3)
OPEN
-
-
-
-
Positioner 1
3)
OPEN
CLOSED
-
-
-
Positioner 2
3)
OPEN
CLOSED
-
-
-
Positioner 3
3)
OPEN
CLOSED
-
-
-
Positioner 4
3)
OPEN
CLOSED
-
-
-
Positioner 5
3)
OPEN
CLOSED
-
-
-
Soft starter
2) 3)
ON line
contactor
-
Reset
ON command -
Soft starter with reversing
contactor
3)
RIGHT line
contactor
LEFT line
contactor
Reset
ON command -