Tables, data records
3.3 Tables, PROFIBUS data records
SIMOCODE pro - Communication
178
Function Manual, 11/2018, A5E40508495002A/RS-AC/003
Byte.Bit Designation (PRM group)
Type Range
Unit
Default Note
Information
18.2
Warning response I<
Bit[2] 0, 1, 2
0
BU0 BU1 BU2(+)
18.4
Stalled rotor - Response
Bit[2] 0, 1, 2, 3
0
BU0 BU1 BU2(+)
18.6
EM+
1)
- response to sensor
fault
Bit[2] 0, 1, 2, 3
0
BU0 BU2(+)
19.0
Monitoring the number of
starts - Response to
overshoot
Bit[2] 0, 1, 2, 3
0
BU0 BU1 BU2(+)
19.2
Monitoring the number of
starts - Response to
prewarning
Bit[2] 0, 1, 2
0
BU0 BU1 BU2(+)
19.4
Motor operating hours
monitoring - Response
Bit[2] 0, 1, 2
0
BU0 BU1 BU2(+)
19.6
Motor stop time monitoring
- Response
Bit[2] 0, 1, 2
0
BU0 BU1 BU2(+)
20.0
External fault 1 - Response Bit[2] 1, 2, 3
1
BU0 BU1 BU2(+)
20.2
External fault 2 - Response Bit[2] 1, 2, 3
1
BU0 BU1 BU2(+)
20.4
External fault 3 - Response Bit[2] 1, 2, 3
1
BU0 BU1 BU2(+)
20.6
External fault 4 - Response Bit[2] 1, 2, 3
1
BU0 BU1 BU2(+)
21.0
Reserved
Bit[2]
0
21.2
Basic unit - Debounce time
inputs
Bit[2] 0 - 3
10 ms 1
Offset 6 ms
BU0 BU1 BU2(+)
21.4
Timer 1 - Type
Bit[2] 0, 1, 2, 3
0
0 = With closing delay
1 = Closing delay with
memory
2 = With opening delay
3 = With fleeting closing
BU0 BU1 BU2(+)
21.6
Timer 2 - Type
Bit[2] 0, 1, 2, 3
0
BU0 BU1 BU2(+)
22.0
Signal conditioning 1 - Type Bit[2] 0, 1, 2, 3
0
0 = Non-inverting
1 = Inverting
2 = Edge rising with
memory
3 = Edge falling with
memory
BU0 BU1 BU2(+)
22.2
Signal conditioning 2 - Type Bit[2] 0, 1, 2, 3
0
BU0 BU1 BU2(+)
22.4
Non-volatile element 1 -
Type
Bit[2] 0, 1, 2, 3
0
BU0 BU1 BU2(+)
22.6
Non-volatile element 2 -
Type
Bit[2] 0, 1, 2, 3
0
BU0 BU1 BU2(+)
23.0
EM+
2)
- monitoring
Bit[2] 0, 1, 2, 3
0
0 = on
1 = on+
2 = run
3 = run+
BU0 BU2(+)
23.2
EM+
2)
- monitoring warning Bit[2] 0, 1, 2, 3
0
BU0 BU2(+)
23.4
EM - response to an
external ground fault
Bit[2] 1, 3
1
0 = disabled
1 = signaling
2 = warn
3 = tripping
BU0 BU1 BU2(+)
23.6
EM - response to warning
of an external ground fault
Bit[2] 0, 1, 2,
0
BU0 BU1 BU2(+)
24.0
Part - Bit[4] parameters
24.0
External fault 1 - Reset also
by
Bit[4] 0 -
1111B
0101B Bit[0] = Panel reset
Bit[1] = Auto-reset
Bit[2] = Remote reset
BU0 BU1 BU2(+)
24.4
External fault 2 - Reset also
by
Bit[4] 0 -
1111B
0101B
BU0 BU1 BU2(+)