Tables, data records
3.4 Tables, PROFINET data records
SIMOCODE pro - Communication
256
Function Manual, 11/2018, A5E40508495002A/RS-AC/003
Byte.Bit
Designation (PRM group)
Type
Range
Unit
Default
Note
Info
28.0
Bit[4] - Parameters (25)
28.0
TM1 - sensor type
Bit[3] +
Bit
000B to 1
00B
000B
000B = PT100
001B = PT100
010B = KTY83
011B = KTY84
100B = NTC
TM1
28.4
OPD language
Bit[4]
0 - 7
1
0 = English
1 = German
2 = French
3 = Polish
4 = Spanish
5 = Portuguese
6 = Italian
7 = Finnish
29.0
External fault 5 - Reset also
by
Bit[4]
0 - 1111B
0101B
Bit[0] = Panel reset
Bit[1] = Auto-reset
Bit[2] = Remote
reset
Bit[3] = OFF
command reset
29.4
External fault 6 - Reset also
by
Bit[4]
0 - 1111B
0101B
30.0
OPD - Contrast (bit 0 to 3)
Bit[4]
0 - 255
1 %
50
30.4
OPD - Contrast (bit 4 to 7)
Bit[4]
31.0
OPD - Profile (bit 0 to 3)
Bit[4]
0 - 26
0
31.4
OPD - Profile (bit 4 to 7)
Bit[4]
32.0
Truth table 7 type 2I/1O
Bit[4]
0 - 1111B
0
32.4
Truth table 8 type 2I/1O
Bit[4]
0 - 1111B
0
33.0
I
s
1 conversion factor -
Denominator
Bit[4]
0 - 15
0
33.4
I
s
2 conversion factor -
Denominator
Bit[4]
0 - 15
0
34.0
Hysteresis P - Cos phi - U
Bit[4]
0 - 15
5
1 %
UM(+)
34.4
Hysteresis 0/4-20 mA
Bit[4]
0 - 15
5
1 %
AM1 AM2
35.0
Hysteresis free limits
Bit[4]
0 - 15
5
1 %
35.4
OPD - Lighting
Bit[4]
0 - 4
2
0 = Off
1 = 3 s
2 = 10 s
3 = 1 min
4 = 5 min
36.0
Byte parameters (29)
36.0
Reserved
Byte
0
37.0
EM - Delay
Byte
0 - 255
100 ms
5
EM
38.0
Trip level cos phi<
Byte
0 - 100
1 %
0
UM(+)
39.0
Warning level cos phi<
Byte
0 - 100
1 %
0
UM(+)