Tables, data records
3.2 Assignment of cyclic receive and send data for predefined control functions
SIMOCODE pro - Communication
Function Manual, 11/2018, A5E40508495002A/RS-AC/003
139
3.2.12
Positioner
Table 3- 15 Assignment of cyclic receive / send data, positioner
Cyclic receive data
Bit 0.0
Device parameters
→ Motor control → Control stations → PLC/PCS [DP] → Close
Bit 0.1
Device parameters → Motor control → Control stations → PLC/PCS [DP] → Stop
Bit 0.2
Device parameters → Motor control → Control stations → PLC/PCS [DP] → Open
Bit 0.3
Further function bloc
ks → Standard functions → Test / Reset → Test1
- Input
Bit 0.4
Further function blocks → Standard functions → Emergency start → Emergency start
- Input
Bit 0.5
Device parameters → Motor control → Control stations → Mode selector S1
Bit 0.6
Further function blocks
→
Standard functions
→
Test / Reset
→
Reset 1 - Input
Bit 0.7
Not connected
Bit 1.0
Not connected
Bit 1.1
Not connected
Bit 1.2
Not connected
Bit 1.3
Not connected
Bit 1.4
Not connected
Bit 1.5
Not connected
Bit 1.6
Not connected
Bit 1.7
Not connected
Byte 2/3 *) (analog value)
Not connected
Cycl. send data
Bit 0.0
Status - ON < (CLOSED)
Bit 0.1
Status - OFF (Stop)
Bit 0.2
Status - ON > (OPEN)
Bit 0.3
Event - Prewarning overload (I>115 %)
Bit 0.4
Status - Interlocking time active
Bit 0.5
Status - Remote mode
Bit 0.6
Status - General fault
Bit 0.7
Status - general warning
Bit 1.0
Status - positioner runs in OPEN direction
Bit 1.1
Not connected
Bit 1.2
Status - positioner runs in CLOSED direction
Bit 1.3
Not connected
Bit 1.4
Not connected
Bit 1.5
Not connected
Bit 1.6
Not connected
Bit 1.7
Not connected
Byte 2/3 (analog value)
Maximum current I_max
Byte 4/5 *) (analog value)
Not connected
Byte 6/7 *) (analog value)
Not connected
Byte 8/9 *) (analog value)
Not connected
*) for SIMOCODE pro V / pro S, basic type 1 only