Tables, data records
3.5 Modbus data tables
SIMOCODE pro - Communication
Function Manual, 11/2018, A5E40508495002A/RS-AC/003
307
Input/holding register Designation
Type Range
Unit
Default Comments
Access
1)
Info
Address high/
low
Bit
low
0-3 Is1 conversion
factor - Denominator
Bit[4] 0 ... 15
0
r
4-7 Is2 conversion
factor - Denominator
Bit[4] 0 ... 15
0
r
0x4391 high 0-3 Hysteresis P -
cos phi - U
Bit[4] 0 ... 15 1 %
5
r
4-7 Hysteresis 0/
4-20 mA
Bit[4] 0 ... 15 1 %
5
r
low
0-3 Hysteresis free limits Bit[4] 0 ... 15 1 %
5
r
4-7 OPD - Lighting
Bit[4] 0 ... 4
2
0 = OFF
1 = 3 s
2 = 10 s
3 = 1 min
4 = 5 min
r
from E03
Part - Byte
parameters
0x4392
high
Byte
r
low
EM - Delay
Byte 0 ... 255 100
ms
5
r/w
EM
0x4393
high
Trip level cos phi<
Byte 0 ... 100 1 %
0
r/w
UM
low
Warning
level cos phi<
Byte 0 ... 100 1 %
0
r/w
UM
0x4394
high
Trip level U<
Byte 0 ... 255 8 V
0
r/w
UM
low
Warning level U<
Byte 0 ... 255 8 V
0
r/w
UM
0x4395
high
Trip level 0/
4-20 mA>
Byte 0 ... 255 *128 0
r/w
AM1
low
Warning level 0/
4-20mA>
Byte 0 ... 255 *128 0
r/w
AM1
0x4396
high
Trip level 0/
4-20 mA<
Byte 0 ... 255 *128 0
r/w
AM1