Tables, data records
3.4 Tables, PROFINET data records
SIMOCODE pro - Communication
Function Manual, 11/2018, A5E40508495002A/RS-AC/003
205
Node ID
Data type
Description
GG3
GG3 GP
125
Boolean
Status - Positioner running in close direction
✓
—
126
Boolean
Status - Feedback closed (FC)
✓
—
127
Boolean
Status - Feedback open (FO)
✓
—
128
Boolean
Status - Torque closed (TC)
✓
—
129
Boolean
Status - Torque open (TO)
✓
—
130
Boolean
Status - Test position (TPF)
✓
✓
131
Boolean
Status - Operational Protection OFF (OPO)
✓
—
132
Boolean
Status - Remote mode
✓
✓
133
Boolean
Status - Emergency start executed
✓
✓
134
Boolean
Status - Cooling down period active
✓
✓
135
Boolean
Status - Pause time active
✓
✓
136
Boolean
Status - Device test active
✓
✓
137
Boolean
Status - Phase-sequence 1-2-3
✓
—
138
Boolean
Status - Phase-sequence 3-2-1
✓
—
139
Boolean
Status - Enabling circuit closed
✓
—
Diagnostic events
140
Boolean
Event - Prewarning overload (I>115%Is)
✓
✓
141
Boolean
Event - Unbalance
✓
✓
142
Boolean
Event - Overload
✓
✓
143
Boolean
Event - Ov loss of phase
✓
✓
144
Boolean
Event - Internal ground fault
✓
✓
145
Boolean
Event - External Ground Fault
✓
✓
146
Boolean
Event - Warning external ground fault
✓
✓
147
Boolean
Event - Thermistor trip level
✓
✓
148
Boolean
Event - Thermistor short circuit
✓
✓
149
Boolean
Event - Thermistor open circuit
✓
✓
150
Boolean
Event - TM1 warning level T>
✓
✓
151
Boolean
Event - TM1 trip level T>
✓
✓
152
Boolean
Event - TM1 sensor fault
✓
✓
153
Boolean
Event - TM1 out of range
✓
✓
154
Boolean
Event - EM Open Circuit
✓
✓
155
Boolean
Event - EM Short Circuit
✓
✓
156
Boolean
Event - Warning level I>
✓
✓
157
Boolean
Event - Warning level I<
✓
✓
158
Boolean
Event - Warning level P>
✓
—
159
Boolean
Event - Warning level P<
✓
—
160
Boolean
Event - Warning level cos phi<
✓
—
161
Boolean
Event - Warning level U<
✓
—
162
Boolean
Event - AM1 warning level 0/4-20mA>
✓
—
163
Boolean
Event - AM1 warning level 0/4-20mA<
✓
—
164
Boolean
Event - Trip level I>
✓
✓
165
Boolean
Event - Trip level I<
✓
✓