Tables, data records
3.4 Tables, PROFINET data records
SIMOCODE pro - Communication
Function Manual, 11/2018, A5E40508495002A/RS-AC/003
233
Byte.Bit Designation
Information
PNIO
diagnostic
status **)
PNIO error
number (channel
error type)
Error no.
16.4
Event - Initialization module
write-protected, parameter
changes not allowed
1
0x0010
16.5
Events - Memory
module -
initialization
module (InM)
Event - Memory module
write-protected
16.6
Event - Initialization module
write-protected
16.7
Event - Initialization module
identification data write-
protected
17.0
Warnings -
Protection
Warning - Overload operation
IM UM(+)
2
0x1020
17.1
Warning - Unbalance
IM UM(+)
2
0x1021
17.2
Warning - Overload
IM UM(+)
2
0x1022
17.3
Warning - Ov phase
failure
IM UM(+)
2
0x1023
17.4
Warning - Internal ground fault IM UM(+)
2
0x1027
17.5
Warning - External ground fault EM
2
0x1028
17.6
Reserved
17.7
Warning - Thermistor overload Th
2
0x1024
18.0
Warning - Thermistor short
circuit
Th
2
0x1025
18.1
Warning - Thermistor open
circuit
Th
2
0x1026
18.2
Warning - TM1 warning T >
TM1
2
0x102B
18.3
Reserved
18.4
Warning - TM1 sensor fault
TM1
2
0x102C
18.5
Warning - TM1 out of range
TM1
2
0x102D
18.6
Warning - EM+ open circuit
EM+
1)
2
0x1029
18.7
Warning - EM+ short-circuit
EM+
1)
2
0x102A
19.0
Warnings - Level
monitoring
Warning - Warning I>
IM UM(+)
2
0x1040
19.1
Warning - Warning I<
IM UM(+)
2
0x1041
19.2
Warning - Warning P>
UM(+)
2
0x1042
19.3
Warning - Warning P<
UM(+)
2
0x1043
19.4
Warning - Warning cos phi<
UM(+)
2
0x1045
19.5
Warning - Warning U<
UM(+)
2
0x1047
19.6
Warning - Warning 0/4-20 mA> AM1
2
0x1048
19.7
Warning - Warning 0/4-20 mA< AM1
2
0x1049
20.0
Warning - Stalled rotor
IM UM(+)
2
0x104C
20.1
Reserved bit [2]